SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)

35
CAUTION
Indoors
Power supply
Please use the shielded wire, and the shield layer must be grounded.
On/Off switch
Fuse
Distribution box Distribution box Distribution box Distribution box
Fuse Fuse Fuse
L N
L N L N
L N
Master unit
Slave unit 1
H1 H2
Slave unit 2
H1 H2
Slave unit x
H1 H2
Build-out resistor
Only the last IDU
requires adding the
build-out resistor at
H1 and H2.
......
Power supply
Please use the shielded wire, and the shield layer must be grounded.
On/Off switch
Fuse
Distribution box Distribution box Distribution box Distribution box
The cascade system electrical control system connection diagram(3N~)
Master unit
Slave unit 1
H1 H2
Slave unit 2
H1 H2
Slave unit x
H1 H2
Build-out resistor
Only the last IDU
requires adding the
build-out resistor at
H1 and H2
......
L1
L2 L3 N
Fuse
L1
L2 L3 N
Fuse
L1 L2 L3 N
Fuse
L1 L2 L3 N
The cascade system electrical control system connection diagram(1N~)
ON
OFF
SW9
Slave unit
Master unit
ON
OFF
SW9
Slave unit
Master unit
X/HA Y/HB
X/HA Y/HB
1. The cascade function of the system only supports 6 machines at most.
2. In order to ensure the success of automatic addressing, all machines must be connected to the same power supply and
powered on uniformly.
3. Only the Master unit can connect the controller, and you must put the SW9 to β€œon” of the master unit, the slave unit cannot
connect the controller .
4.Please use the shielded wire, and the shield layer must be grounded.