SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)
Table Of Contents
34
9.6.5 Remove the switch box cover
NOTE
Unit 5kW 7kW 9kW 12kW 14kW 16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18 18 18 30 30 30 14 14 14
Wiring size(mm
2
)
4.0 4.0 4.0 6.0 6.0 6.0 2.5 2.5 2.5
1-phase 5-16kW standard and 3-phase 12-16kW standard
UNIT POWER SUPPLY
1-phase
L N
L N
LPS
FUSE
UNIT POWER SUPPLY
3-phase
LPS
FUSE
L1 NL2 L3
L3
N
L2L1
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
Stated values are maximum values (see electrical data for exact values).
Leakage protection switch must be installed to the power supply of the unit.