SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)
Table Of Contents
- EDM SYSHP MINI EVO-P_GB_cover.pdf
- SYSHP MINI EVO-P_EDM_EN.pdf
- Front Cover.pdf
- CONTENTS.pdf
- Part 1 General Information.pdf
- Part 3 Insatllation and Field Settings.pdf
- 1 User Interface Field Settings
- 1.1 Introduction
- 1.2 Menu Structure
- 1.3 FOR SERVICEMAN Menu
- 1.4 DHW MODE SETTING Menu
- 1.5 COOL MODE SETTING Menu
- 1.6 HEAT MODE SETTING Menu
- 1.7 AUTO MODE SETTING Menu
- 1.8 TEMP. TYPE SETTING Menu
- 1.9 ROOM THERMOSTAT Menu
- 1.10 OTHER HEATING SOURCE Menu
- 1.11 HOLIDAY AWAY SETTING Menu
- 1.12 SERVICE CALL Menu
- 1.13 RESTORE FACTORY SETTINGS
- 1.14 TEST RUN
- 1.15 SPECIAL FUNCTION
- 1.16 AUTO RESTART
- 1.17 POWER INPUT LIMITATION
- 1.18 INPUT DEFINE
- 1.19 CASCADE SET
- 1.20 HMI ADDRESS SET
- 1.21 COMMON SET
- 2 Operation parameter
- 1 User Interface Field Settings
80
The following parameter ranges are used to roughly determine whether the system is running properly:
Discharge temperature(Tp) for heating/DHW mode
T4<-10℃
Twout+15<Tp<Tw_out+40
-10℃≤T4<10℃
Twout+10<Tp<Tw_out+35
10℃≤T4<25℃
Twout+10<Tp<Tw_out+30
T4≥25℃
Twout+10<Tp<Tw_out+28
Note:
T4 means ambient temperature
Tw_out means leaving water temperature.
Discharge pressure(P1) for heating/DHW mode
Tw_out(℃)
25
30
35
40
45
50
55
60
65
P1(kPa)
1750±
150
2000±
150
2270±
150
2560±
150
2890±
150
3250±
150
3630±
150
3900±
150
4200±
150
Note: P1 is absolute pressure.
Discharge temperature(Tp) for cooling mode
Tp
Fx<44Hz
44Hz≤Fx<62Hz
62Hz≤Fx<72Hz
Fx≥72Hz
T4<25℃
52±10
56±10
58±10
62±10
25℃≤T4<30℃
56±10
62±10
68±10
74±10
30℃≤T4<35℃
65±10
70±10
75±10
80±10
35℃≤T4<40℃
70±10
75±10
80±10
85±10
40℃≤T4<46℃
75±10
80±10
85±10
90±10
T4≥46℃
78±10
80±10
85±10
90±10
Note: Fx means compressor operating frequency.
Suction pressure(P1) for cooling mode
Tw_out(℃)
5~7
8~10
11~13
14~16
17~19
20~22
23~25
P1(kPa)
880±100
955±100
1050±100
1150±100
1250±100
1360±100
1500±100
Note: P1 is absolute pressure.