The following parameter ranges are used to roughly determine whether the system is running properly:
Discharge temperature(Tp) for heating/DHW mode
T4-10
Twout+15TpTw_out+40
-10℃≤T410
Twout+10TpTw_out+35
10℃≤T425
Twout+10TpTw_out+30
T425
Twout+10TpTw_out+28
Note:
T4 means ambient temperature
Tw_out means leaving water temperature.
Discharge pressure(P1) for heating/DHW mode
Tw_out()
25
30
35
40
45
50
55
60
65
P1kPa
1750±
150
2000±
150
2270±
150
2560±
150
2890±
150
3250±
150
3630±
150
3900±
150
4200±
150
Note: P1 is absolute pressure.
Discharge temperature(Tp) for cooling mode
Tp
Fx44Hz
44HzFx62Hz
62HzFx72Hz
Fx72Hz
T425
52±10
56±10
58±10
62±10
25℃≤T430
56±10
62±10
68±10
74±10
30℃≤T435
65±10
70±10
75±10
80±10
35℃≤T440
70±10
75±10
80±10
85±10
40℃≤T446
75±10
80±10
85±10
90±10
T446
78±10
80±10
85±10
90±10
Note: Fx means compressor operating frequency.
Suction pressure(P1) for cooling mode
Tw_out()
57
810
1113
1416
1719
2022
2325
P1kPa
880±100
955±100
1050±100
1150±100
1250±100
1360±100
1500±100
Note: P1 is absolute pressure.