SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)
Table Of Contents
- EDM SYSHP MINI EVO-P_GB_cover.pdf
- SYSHP MINI EVO-P_EDM_EN.pdf
- Front Cover.pdf
- CONTENTS.pdf
- Part 1 General Information.pdf
- Part 3 Insatllation and Field Settings.pdf
- 1 User Interface Field Settings
- 1.1 Introduction
- 1.2 Menu Structure
- 1.3 FOR SERVICEMAN Menu
- 1.4 DHW MODE SETTING Menu
- 1.5 COOL MODE SETTING Menu
- 1.6 HEAT MODE SETTING Menu
- 1.7 AUTO MODE SETTING Menu
- 1.8 TEMP. TYPE SETTING Menu
- 1.9 ROOM THERMOSTAT Menu
- 1.10 OTHER HEATING SOURCE Menu
- 1.11 HOLIDAY AWAY SETTING Menu
- 1.12 SERVICE CALL Menu
- 1.13 RESTORE FACTORY SETTINGS
- 1.14 TEST RUN
- 1.15 SPECIAL FUNCTION
- 1.16 AUTO RESTART
- 1.17 POWER INPUT LIMITATION
- 1.18 INPUT DEFINE
- 1.19 CASCADE SET
- 1.20 HMI ADDRESS SET
- 1.21 COMMON SET
- 2 Operation parameter
- 1 User Interface Field Settings
7
4 System Design and Unit Selection
4.1 Selection Procedure
Step 1: Total heat load calculation
Calculate conditioned surface area
Select the heat emitters (type, quantity, water temperature and heat load)
Step 2: System configuration
Decide whether to include AHS and set AHS’s switching temperature
Decide whether backup electric heater is enabled or disabled
Step 3: Selection of outdoor units
Determine required total heat load on outdoor units
Set capacity safety factor
Select power supply
Provisionally select SYSHP MINI unit capacity based on nominal capacity
Correct capacity of the outdoor units for the following items:
Outdoor air temperature / Outdoor humidity / Water outlet temperature
1
/
Altitude / Anti-freeze fluid
Is corrected SYSHP MINI unit capacity ≥ Required total heat load on outdoor
units
2
Yes No
SYSHP MINI system selection
is complete
Select a larger model or enable
backup electric heater operation
Notes:
1. If the required water temperatures of the heat emitters are not all the same, the
SYSHP MINI’s outlet water temperature setting should be set at the highest
of the heat emitter required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor unit's
capacity table, calculate the corrected capacity by interpolation.
2. If the outdoor unit selection is to be based on total heating load and total cooling load, select Mono units which satisfy not only the total heating load
requirements but also the total cooling load requirements.