74
1.14.4 COOL MODE RUNNING operation
MENU > FOR SERVICEMAN > TEST RUN > COOL MODE RUNNING
The COOL MODE RUNNING operation is used to check the operation of the system in
space cooling mode.
During the COOL MODE RUNNING operation, the leaving water set temperature is
7°C. The current actual leaving water temperature is displayed on the user interface.
The unit operates until the leaving water temperature drops to the set temperature
or the next command is received.
1.14.5 HEAT MODE RUNNING operation
The HEAT MODE RUNNING operation is used to check the operation of the system
in space heating mode.
During HEAT MODE test running, the default target outlet water temperature is
35°C. The IBH (backup heater) will turn on after the compressor runs for 10 min.
After the IBH runs for 3 minutes, the IBH will turn off, the heat pump will operate
until the water temperature increase to a certain value or the next command is
received.
1.14.6 DHW MODE RUNNING operation
The DHW MODE RUNNING operation is used to check the operation of the system in DHW mode.
During DHW MODE test running, the default target temperature of the domestic water is 55°C. The TBH(tank boost heater)
will turn on after the compressor runs for 10min. The TBH will turn off 3 minutes later, the heat pump will operate until the
water temperature increase to a certain value or the next command is received.
DHW MODE RUNNING display
1.15 SPECIAL FUNCTION
1.15.1 SPECIAL FUNCTION menu overview
MENU > FOR SERVICEMAN > SPECIAL FUNCTION
SPECIAL FUNCTION is used to pre-heating floor and
drying up floor once installation is complete or the first
time start up the unit or restart the unit after a long time
stop.
11 TEST RUN
TEST RUN IS ON.
DHW MODE IS ON.
LEAVINGWATER TEMPERATURE IS 15°C
WATER TANK TEMPERATURE IS 13°C
CONFIRM
COOL MODE RUNNING display
HEAT MODE RUNNING display
Special functions menu
11 TEST RUN
TEST RUN IS ON.
COOL MODE IS ON.
LEAVING WATER TEMPERATURE IS
15°C.
CONFIRM
11 TEST RUN
TEST RUN IS ON.
HEAT MODE IS ON.
LEAVING WATER TEMPERATURE IS
15°C.
CONFIRM
12 SPECIAL FUNCTION
ACTIVE THE SETTINGS AND ACTIVE THE
“SPECIAL FUNCTION”?
CONFIRM
NO
YES
ENTER
12 SPECIAL FUNCTION
12.1 PREHEATING FOR FLOOR
12.2 FLOOR DRYING UP