SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)

66
t_INTERVAL_C sets the cooling mode compressor re-start delay. When the compressor stops running, it will not re-start
until at least t_INTERVAL_C minutes have elapsed.
T1SetC1 sets the water temperature 1 of personalized setting curve for cooling mode.
T1SetC2 sets the water temperature 2 of personalized setting curve for cooling mode.
T4C1 sets the ambient temperature 1 of personalized setting curve for cooling mode.
T4C2 sets the ambient temperature 2 of personalized setting curve for cooling mode.
ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode. (FCU: Fan coil unit; FHL: Floor heating loop; RAD.:
Radiator)
ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode. (FCU: Fan coil unit; FHL: Floor heating loop; RAD.:
Radiator)
1.6 HEAT MODE SETTING Menu
MENU > FOR SERVICEMAN > HEAT MODE SETTING
HEAT MODE SETTING menu
HEAT MODE enables or disables heating mode.
t_T4_FRESH_H sets the refresh time of heating mode climate temperature curve.
T4HMAX sets the ambient temperature above which the heat
pump will operate heating mode with lowest compressor
frequency.
T4HMIN sets the ambient temperature below which the heat
pump will not operate in heating mode.
dT1SH sets the temperature difference between the heat pump leaving water temperature (T1) and the heat pump leaving
water set temperature (T1S) above which the heat pump provides hot water to the space heating terminals.
T1S
HEATING OFF
T1
T1S-dT1SH
HEATING ON
16°C
-15°C
5°C
2.0Hrs
YES
3 HEAT MODE SETTING
3.1 HEAT MODE
3.2 t_T4_FRESH_H
3.3 T4HMAX
3.4 T4HMIN
3.5 dT1SH
ADJUST
1/3
35°C
28°C
-5°C
5MIN
2
° C
3 HEAT MODE SETTING
3.6 dTSH
3.7 t_INTERVAL_H
3.8 T1SetH1
3.9 T1SetH2
3.10 T4H1
ADJUST
2/3
FHL
RAD.
7° C
3 HEAT MODE SETTING
3.11 T4H2
3.12 ZONE1 H-EMISSION
3.13 ZONE2 H-EMISSION
3.14 FORCE DEFROST
ADJUST
3/3
NON
T4HMAX, T4HMIN
OFF
HEAT
HEAT(Lowest
compressor
frequency)
T4HMIN
T4HMAX
T4
Abreviations:
T4: Outdoor ambient temperature