SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)
Table Of Contents
- EDM SYSHP MINI EVO-P_GB_cover.pdf
- SYSHP MINI EVO-P_EDM_EN.pdf
- Front Cover.pdf
- CONTENTS.pdf
- Part 1 General Information.pdf
- Part 3 Insatllation and Field Settings.pdf
- 1 User Interface Field Settings
- 1.1 Introduction
- 1.2 Menu Structure
- 1.3 FOR SERVICEMAN Menu
- 1.4 DHW MODE SETTING Menu
- 1.5 COOL MODE SETTING Menu
- 1.6 HEAT MODE SETTING Menu
- 1.7 AUTO MODE SETTING Menu
- 1.8 TEMP. TYPE SETTING Menu
- 1.9 ROOM THERMOSTAT Menu
- 1.10 OTHER HEATING SOURCE Menu
- 1.11 HOLIDAY AWAY SETTING Menu
- 1.12 SERVICE CALL Menu
- 1.13 RESTORE FACTORY SETTINGS
- 1.14 TEST RUN
- 1.15 SPECIAL FUNCTION
- 1.16 AUTO RESTART
- 1.17 POWER INPUT LIMITATION
- 1.18 INPUT DEFINE
- 1.19 CASCADE SET
- 1.20 HMI ADDRESS SET
- 1.21 COMMON SET
- 2 Operation parameter
- 1 User Interface Field Settings
65
PUMP_D TIMER enable or disable the DHW pump run as timed and keeps running for PUMP_D RUNNING TIME
PUMP_D RUNNING TIME set the certain time that the DHW pump will keep running
PUMP_D DISINFECT enable or disable the DHW pump operates when heat pump is in disinfect mode and T5S_DI- T5≤2
ACS FUNCTION enable or disable the second water tank control T5_2
1.5 COOL MODE SETTING Menu
MENU > FOR SERVICEMAN > COOL MODE SETTING
COOL MODE SETTING menu
COOL MODE enables or disables cooling mode. For installations with space cooling terminals, select YES to enable cooling
mode. For installations without space cooling terminals, select NON to disable cooling mode.
t_T4_FRESH_C sets the refresh time of cooling mode climate temperature curve.
T4CMAX sets the ambient temperature above which the heat pump will operate
in cooling mode with lowest compressor frequency.
T4CMIN sets the ambient temperature below which the heat pump will not
operate in cooling mode.
dT1SC sets the minimum temperature difference between the heat pump
leaving water temperature (T1) and the heat pump leaving water set
temperature (T1S) at which the heat pump provides chilled water to the
space cooling terminals. When T1 – T1S ≥ dT1SC the heat pump provides
chilled water to the space cooling terminals and when T1 ≤ T1S the heat
pump does not provide chilled water to the space cooling terminals.
dTSC sets the temperature difference between the actual room
temperature (Ta) and set room temperature (TS) above which the
heat pump provides chilled water to the space cooling terminals.
When Ta – TS ≥ dTSC the heat pump provides chilled water to the
space cooling terminals and when Ta ≤ TS the heat pump does not
provide chilled water to the space cooling terminals. dTSC is only applicable if YES is selected for ROOM TEMP in the 5
TEMP. TYPE SETTING menu.
43°C
20°C
5°C
2.0Hrs
YES
1/3
2 COOL MODE SETTING
2.1 COOL MODE
2.2 t_T4_FRESH_C
2.3 T4CMAX
2.4 T4CMIN
2.5 dT1SC
ADJUST
2° C
5MIN
10°C
16°C
35°C
2/3
2 COOL MODE SETTING
2.6 dTSC
2.7 t_INTERVAL_C
2.8 T1SetC1
2.9 T1SetC2
2.10 T4C1
ADJUST
25° C
FCU
FHL
3/3
2 COOL MODE SETTING
2.11 T4C2
2.12 ZONE1 C-EMISSION
2.13 ZONE2 C-EMISSION
ADJUST
T4CMAX, T4CMIN
OFF
COOL
COOL(Lowest
compressor
frequency)
T4CMIN
T4CMAX
T4
Abreviations:
T4: Outdoor ambient temperature
dT1SC
TS
HEATING OFF
Ta
TS-dTSH
HEATING ON
Abreviations:
T1: Heat pump leaving water temperature
T1S: Heat pump leaving water set temperature
dTSC
TS+dTSC
COOLING ON
Ta
TS
COOLING OFF