SYSHP MINI EVO P Engineering Data Manual (EDM SYSHP MINI EVO P S 1GB)
Table Of Contents
- EDM SYSHP MINI EVO-P_GB_cover.pdf
- SYSHP MINI EVO-P_EDM_EN.pdf
- Front Cover.pdf
- CONTENTS.pdf
- Part 1 General Information.pdf
- Part 3 Insatllation and Field Settings.pdf
- 1 User Interface Field Settings
- 1.1 Introduction
- 1.2 Menu Structure
- 1.3 FOR SERVICEMAN Menu
- 1.4 DHW MODE SETTING Menu
- 1.5 COOL MODE SETTING Menu
- 1.6 HEAT MODE SETTING Menu
- 1.7 AUTO MODE SETTING Menu
- 1.8 TEMP. TYPE SETTING Menu
- 1.9 ROOM THERMOSTAT Menu
- 1.10 OTHER HEATING SOURCE Menu
- 1.11 HOLIDAY AWAY SETTING Menu
- 1.12 SERVICE CALL Menu
- 1.13 RESTORE FACTORY SETTINGS
- 1.14 TEST RUN
- 1.15 SPECIAL FUNCTION
- 1.16 AUTO RESTART
- 1.17 POWER INPUT LIMITATION
- 1.18 INPUT DEFINE
- 1.19 CASCADE SET
- 1.20 HMI ADDRESS SET
- 1.21 COMMON SET
- 2 Operation parameter
- 1 User Interface Field Settings
13
Sound power level
2
Heating A7W35 dB 70 72 72
Heating max dB 74 74 74
Heating slince mode 1 dB 66 67 67
Heating slince mode 2 dB 64 64 64
Cooling A35W18 dB 69 71 71
Cooling max dB 74 74 74
Cooling slince mode1 dB 66 67 67
Cooling slince mode2 dB 63 64 64
Compressor Type DC twin rotary DC twin rotary DC twin rotary
Fan
Type DC motor DC motor DC motor
Number 1 1 1
Air flow m
3
/h 5200 5200 5200
Air side heat exchanger Type Fin coil Fin coil Fin coil
Throttle Type Electronic expansion valve
Refrigerant
Type R32 R32 R32
Charged volume kg 1.8 1.8 1.8
Water side heat exchanger Type Plate Plate Plate
Rated water flow m
3
/h 2.10 2.43 2.75
Water flow range m
3
/h 0.70~2.50 0.70~2.75 0.70~3.00
Water pump
Type DC DC DC
Maximum pump head m 9 9 9
Expansion vessel
Volume L 5 5 5
Maximum working pressure bar 8 8 8
Safety valve MPa 0.3 0.3 0.3
Flow switch m
3
/h 0.6 0.6 0.6
Water side connection G5/4"BSP G5/4"BSP G5/4"BSP
Unit dimension (W×H×D) mm 865×1040×410 865×1040×410 865×1040×410
Packing dimension (W×H×D) mm 970×1190×560 970×1190×560 970×1190×560
Net weight kg 106 106 106
Gross weight kg 122 122 122
Ambient temperature range
Cooling
⁰C
-5~43 -5~43 -5~43
Heating
⁰C
-25~35 -25~35 -25~35
DHW
⁰C
-25~43 -25~43 -25~43
Water setting temperature range
Cooling
⁰C
5~25 5~25 5~25
Heating
⁰C
25~65 25~65 25~65
DHW
⁰C
20~60 20~60 20~60
Note:
1. The above data test reference standard EN14511; EN14825; EN50564; EN12102; (EU) No:811/2013; (EU)No:813/2013; OJ 2014/C 207/02.
2. Sound power test condition:EN12102-1