IOM BACNET GATEWAY
4
PART 2. BACNET FUNCTION OVERVIEW
1 Applications
2 Features
3 Specifications
4 Statement on Conformity of BACnet Protocol
Implementation
It is used for communications between the VRF system and the building management system
that has the BACnet interface, to integrate the VRF system with the building management
system.
Connect the VRF system to the BACnet network.
Support IMMP-BAC(A) protocols, and comply with BACnet standards.
Each port can be connected to a maximum of 64 indoor units, and the total number of indoor
and outdoor units on all 4 ports is 384 at most.
Plug-in terminal interface is used to facilitate the wiring.
No. Function Description
1 Input power 24VAC 50/60Hz
2 Communication interface
4X RS485 interface 1X RJ45 Ethernet
port Ethernet port
3 Operating environment Temperature: 0-40°C
4 Weight
800g
4.1 Product Description
4.2 Supported BACnet Consistency Categories
The BACnet gateway monitors the outdoor and indoor VRF units via the RS485 interface,
and communicates with the building management system using the IMMP-BAC(A) interface.
√
□
Category 3