IOM BACNET GATEWAY

14
6.3 Object List for HTHM Units
The BACnet device for each HTHM unit provides the following objects:
Object ID Object Name Current Value Description/Notes R/W
AV 50
Heating-water temperature setting, unit is °C,
range
is 25-80.
RW
AV 51
Heating temperature setting, unit is °C,
range is 25-80.
RW
AV 52
Heating Temperature
Lock
RW
AV 53
Water Heating
Temperature Lock
RW
AV 60
Water Inlet
Temperature
Water Inlet Temperature in °C R
AV 61
Water outlet
Temperature
Water outlet Temperature in °C R
AV 62
Water Tank
Temperature
Water Tank Temperature in °C R
AV 63 Error Code Error Code (see 6.4) R
AV 64 Tf Tf temperature in °C R
AV 65 T2A T2A temperature in °C R
AV 66 T7 T7 temperature in °C R
AV 67 T7C T7C temperature in °C R
AV 68 Pe Pe in bar R
AV 69 Pc Pc in bar R
R
AV 70 EXV 1 EXV 1 opening R
Water Heating
Temperature Setting
Heating Temperature
Setting
The current value, "0", indicates that the limit
of the heating temperature is unlocked,
"25~80°C" indicates the upper limit of the
Heating temperature, "254" indicates the
temperature non-adjustable.
The current value, "0", indicates that the limit
of the Heating-water temperature is unlocked,
"25~80°C" indicates the upper limit of the
Heating-water temperature, "254" indicates
the temperature non-adjustable.
AV 70 EXV 1 EXV 1 opening