IOM BACNET GATEWAY

11
Object ID Object Name Current Value Description R/W
AV 2
Dual Point (Cooling)
Setting
The set cooling temperature for AUTO mode must be
greater than or equal to the set heating temperature
for AUTO mode. Otherwise, the gateway may
automatically change the set cooling temperature to
make its value the same as the set heating
temperature. If non-automatic mode is used, this is
equivalent to AV 1. range is 10-30. (unit: °C)
RW
AV 3
Dual Point (Heating)
Setting
The set heating temperature for AUTO mode must be
less than or equal to the set cooling temperature for
AUTO mode.Otherwise, the gateway may
automatically change the set heating temperature to
make its value the same as the set cooling
temperature. This variable is valid only when the
indoor unit runs in AUTO mode. When not in AUTO
mode, this variable is invalid. range is 10-30. (unit: °C)
RW
AV 4
Cooling Temperature
Limit Setting
The current value, "0", indicates that the lower limit of
the cooling temperature is unlocked, while "17~30°C"
indicates the lower limit of the cooling temperature.
For indoor units that do not support the feature to lock
the lower limit in cooling mode, the setting for this
variable is not valid.
RW
AV 5
Heating Temperature
Limit Setting
The current value, "0", indicates that the upper limit of
the heating temperature is unlocked, while "17~30°C"
indicates the upper limit of the heating temperature.
For indoor units that do not support the feature to lock
the upper limit in heating mode, the setting for this
variable is not valid.
RW
RWAV 6 Swing Setting
0 - Maintain the current swing angel,
0 - Maintain the current swing angel,
1~5 - Swing angle 1-5,
6- Auto swing off,
7- Auto swing on.