IOM BACNET GATEWAY

10
Object ID Object Name Current Value Description R/W
BI 2 Alarm Indication
Indicates the error status of the indoor unit: 0 - No
error; 1 - Error
R
BV 1 On/Off Setting
ON/OFF Settings for Indoor Units0 - OFF 1 - ON.
When ON is selected, the operating mode, fan speed,
and temperature settings are sent based on records
from the most recent time the indoor unit was used. If
the indoor unit is turned off when the gateway first
comes online, the default settings will be cooling at 24
degrees Celsius, with low fan speed (1).
RW
BV 4
Remote Control Lock
Setting
0 - Unlock remote control; 1 - Lock remote control RW
BV 5 Controller Lock Setting 0 - unlock wired controller, 1 - lock wired controller RW
MV 1 Mode Setting RW
MV 2 Fan Speed Setting
Fan speed setting:
Fan speed setting:
1~7: 1~7 fan speed;
8 - AUTO;
9 indicates that the fan is off (only used to show the
status of the fan, cannot set the fan speed to off).
For models with 3 fan speeds: 1, 2 - low fan speed;
3, 4 - mid fan speed; 5, 6, 7- high fan speed.
RW
MV 3 Mode Limit Setting
The current value, "1", indicates the mode limit is
unlocked, "2" indicates the cooling mode is locked,
and "3" indicates the heating mode is locked. For
indoor units that do not support mode lock, the setting
for this variable is not valid.
RW
MV 5 Fan Lock/Unlock
Setting
1~7: 1~7 - Lock fan speed; 8 - Unlock. For models
with 3 fan speeds: 1, 2 - Lock on low fan speed; 3, 4
- Lock on mid fan speed; 5, 6, 7 - Lock on high fan
speed.
RW
AV 1 Temperature Setting Temperature setting, unit is °C, range is 10-30. RW
VRF IDU1-OFF; 2-FAN; 3-COOL;
4-HEAT; 5-AUTO; 6-DRY
HRV unit1-OFF; 2-FREE COOL;
3-HEAT EXCHANGE;
4-BYPASS; 5-AUTO;