IOM BACNET GATEWAY

8
NoteThe control operation of the air conditioner should not be too frequent, so that the
command cannot be executed in time and the command is lost. It is recommended that
commands be spaced at least 200 milliseconds apart.
5.4 BACnet Settings
The BACnet network number is in the range of 2~254. You need to restart the device for the
new settings to take effect. Different gateways must have different BACnet network numbers,
and the same network number cannot be used for other devices. The rules to generate the
BACnet device instance number are as follows:
BACnet device instance number for indoor unit = (BACnet network number * 10000) + (Port
number * 1000) + (Indoor unit address);
BACnet device instance number for outdoor unit = (BACnet network number *10000) + (Port
number *1000) +100+ (Outdoor unit address).
485 port number: 0~3. For the 485 port near the network port, the number is 0. Indoor
unit address: 0~63; outdoor unit address: 0~31.
6Object List
The following describes the abbreviations used for different object types:
Object Type
Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Multi-state Input
Multi-state Output
Multi-state Value
Abbreviation
AI
AO
AV
BI
BO
BV
MI
MO
MV