IMO DVG30 03 2017 Am 10 05 2017
Description
8 DVG 30.03.2017
5 Description
The casing is manufactured from seawater resistant aluminium. The base plate with nozzle consists of pre-galvanized
steel. Impellers with backward-curved blades are welded and galvanized (sizes 355 and 450 have impellers made of
pre-galvanized steel and tabbed). They are fastened together with hub and secured screw directly on to the motor
shaft. Dynamically balanced to ISO 1940 T1, class G6,3.
Serially equipped with B5 electric motor 3x400V~, 50Hz, IP 55, insulation class F, with built-in PTC. On request, the fan
can be equipped with electric motor intended for other voltage/frequency. Electric motor outside air stream is cooled
with fresh air. All sizes are serially equipped with service switch.
Electric motor
Connection
Efficiency class, serially:
Single speed (4 pole, 6 pole, 8 pole)
Y or D
IE2 or IE3 (IE1 exceptions: up to
0,55 kW and 8 pole )
Two speed (4-6, 6-8)
Y/Y
IE1
Two speed (4-8, 6-12) Dahlander
YY/Y
IE1
DVG-EC only: Serially equipped with EC (electronically commutated) high efficiency electric motors for single-phase
supply 200 to 265V, 50/60Hz Hz (sizes 355 and 450), respectively 342 to 506V, 50/60Hz Hz (sizes 560, 630, 800). Pro-
tection class IP 54. Insulation class F. Max. RPM: 1500 RPM, respectively 900 RPM at DVG 800. Prewired with control-
ler and the connection box outside on the casing.
5.1 Technical data
Size
Max. synchronic
RPM at 50 or 60
Hz for
DVG/F400**
Max. nomi-
nal power at
50 Hz*/**
Impeller
diameter
Max.
weight**
DVG/F400
Max.
sound power
level inlet**
Max.
sound power
level outlet**
min-1
kW
mm
kg
dB(A)
dB(A)
315
1500
0,37
325
41
78
77
355
1500
0,37
365
43
81
78
400
1500
0,55
410
47
85
86
450
1500
1,1
454
58
88
88
500
1500
1,5
520
91
90
93
560
1500
2,5
570
107
94
94
630
1500
4,6
650
144
96
101
800
1000
5,5
820
223
96
99
*Motor data (input power P1, current, RPM) and data of the fan are visible on the nameplate and on the test proto-
col.
**DVG-T, DVG/120 and DVG-EC may vary from these data due to special motors
5.2 Dimensions
Please see www.systemair.com.
6 Installation
6.1 Safety information
WARNING
Hazard from falling parts!
Check the base/roof before installation for load capacity/strength.
When selecting the hoisting device and fitting material observe the weight, tendency to vibrations and
shear forces (weight information on the nameplate).