EDM SYSHP MINI SPLIT TANK
22
24
26
28
30
32
34
36
38
-25 -20 -15 -10 0-5 5 10 15 20 25
T1S(℃)
T4(℃)
Curve 1
Curve 2
Curve 3
Curve 4
Curve 5
Curve 6
Curve 7
Curve 8
33
38
43
48
53
58
-25 -20 -15 -10 -5 0 5 10 15 20 25
T1S(℃)
T4(℃)
Curve 1
Curve 2
Curve 3
Curve 4
Curve 5
Curve 6
Curve 7
Curve 8
71
4 Climate Related Curves
The climate related curves can be selected in the user interface, MENU > PRESET TEMPERATURE > WEATHER TEMP. SET.
The curves for heang mode and ECO heang mode are the same but the default curve
is curve 4 in heang mode, while in ECO mode, the default curve is curve 6. The default
curves for cooling mode is curve 4. Once the curve is selected, the leaving water set
temperature (T1s) is determined by the outdoor temperature. In each mode, each
curve from the eight curves in the user interface can be selected.
WEATHER TEMP.SET menu
Leaving water set temperature (⁰C )
Low temperature curves for heang mode
1
Notes:
1. It only has the curves of the low temperature seng for heang, if the low temperature is set for heang.
2. Curve 4 is default in low temperature heang mode and curve 6 is default in ECO mode.
Leaving water set temperature (⁰C )
High temperature curves for heang mode
1
Notes:
1. It only has the curves of the low temperature seng for heang, if the low temperature is set for heang.
2. Curve 4 is default in low temperature heang mode and curve 6 is default in ECO mode.