EDM SYSHP MINI SPLIT TANK
63
1.16 AUTO RESTART
MENU > FOR SERVICEMAN > AUTO RESTART
AUTO RESTART sets whether or not the unit re-applies the user interface sengs
when the power returns following a power failure. Select YES to enable auto restart
or NON to disable auto restart.
If the auto restart funcon is enabled, when the power returns following a power
failure, the unit re-applies the user interface sengs from before the power failure.
If the auto restart funcon is disabled, when the power returns aer a power failure,
the unit won’t auto restart.
1.17 POWER INPUT LIMITATION
MENU > FOR SERVICEMAN > POWER INPUT LIMITATION
POWER INPUT LIMITATION sets the type of power input limitaon and the seng
range is 0-8. If the unit will operate at larger power input, 0 should be selected. If
the unit will operate at a lower power input, 1-8 should be selected and the power
input and capacity will decrease.
Limitaon value (unit:A)
Model No. 0 1 2 3 4 5 6 7 8
4/6kW 18 18 16 15 14 13 12 12 12
8/10kW 19 19 18 16 14 12 12 12 12
12/14kW(1N) 30 30 28 26 24 22 20 18 16
16kW(1N) 14 14 13 12 11 10 9 9 9
12/14kW(3N) 30 30 29 27 25 23 21 19 17
16kW(3N) 14 14 13 12 11 10 9 9 9
1.18 INPUT DEFINE
MENU > FOR SERVICEMAN > INPUT DEFINE
INPUT DEFINE sets sensors and funcons to fulll with installaon.
AUTO RESTART menu
POWER INPUT LIMITATION menu
ON/OFF(M1M2) sets the control funcon of M1M2 for remote ON/OFF of unit or AHS of TBH
SMART GRID sets whether SMART GRID control signal is connected to hydronic PCB.
T1b(Tw2) sets whether T1b sensor exist in the installaon.
Tbt1, Tbt2 set whether balance tank temperature sensors are installed in the balance tank. (Tbt1 sensor, individually purchase;
Tbt2, reserved)
Ta sets the Ta sensor connecon type (HMI: Ta on wired controller; IDU: Ta connected on hydronic PCB)
Ta-adj is an correcon value for Ta.