EDM SYSHP MINI SPLIT TANK
62
Preheang for oor screens
During the oor drying up operaon all buons except OK are inacvated. To exit the oor
drying up operaon, press OK and then select YES when prompted.
Note: In the event of a heat pump malfuncon, oor drying up mode will connue if a
backup electric heater and/or addional heang source is available and congured to
support space heang mode.
FLOOR DRYING UP menu
FLOOR DRYING UP screen
1.15.3 FLOOR DRYING UP
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR
DRYING UP
For newly-installed under-oor heang systems, oor drying
up mode can be used to remove moisture from the oor slab
and suboor to prevent warping or rupture of the oor during
oor heang operaon. There are three phases to the oor
drying up operaon:
▪ Phase 1: gradual temperature increase from a starng point of 25°C to the peak temperature
▪ Phase 2: maintain peak temperature
▪ Phase 3: gradual temperature decrease from the peak temperature to 45°C
t_DRYUP sets the duraon of Phase 1.
t_HIGHPEAK sets the duraon of Phase 2.
t_DRYDOWN is the duraon of Phase 3.
T_DRYPEAK sets the heat pump’s leaving water set temperature for Phase 2.
START TIME sets the oor drying up operaon start me.
START DATE sets the oor drying up operaon start date.
FLOOR DRYING UP sengs
Time