EDM SYSHP MINI SPLIT TANK
60
1.14.6 HEAT MODE RUNNING operaon
The HEAT MODE RUNNING operaon is used to check the operaon of the system
in space heang mode.
During the HEAT MODE RUNNING operaon the Heat Pump Split unit leaving water
set temperature is 35°C. The current actual leaving water temperature is displayed
on the user interface. When the HEAT MODE RUNNING operaon starts, the heat
pump rst runs for 10 mins.
HEAT MODE RUNNING display
DHW MODE RUNNING display
Aer 10 mins:
▪ On systems where an auxiliary heat source (AHS) is installed, the AHS starts and runs for 10 mins (whilst the heat pump
connues running), aer which the AHS stops and the heat pump connues to operate unl the water temperature rises to
the set temperature or the heat mode running operaon is exited by pressing OK.
▪ On systems where a backup electric heater is being used, the backup heater turn on (on models where the backup heater has
a simple on/o control funcon). 3 mins later the backup electric heater will turn o. The heat pump will then operate unl
the water temperature rises to the set temperature or the next command is received.
▪ On systems with no auxiliary heat source (AHS), the heat pump will then operate unl the water temperature rises to the set
temperature or the next command is received.
If any error code is displayed during the cool mode running operaon, the cause should be invesgated. Refer to Part 3, 8.2 “Error
Code table”.
1.14.7 DHW MODE RUNNING operaon
The DHW MODE RUNNING operaon is used to check the operaon of the system in DHW mode.
During the DHW MODE RUNNING operaon, the DHW set temperature is 55°C. On systems where a tank boost heater is installed,
the tank boost heater will turn on once the heat pump has run for 10 mins. The tank boost heater will turn o 3 min later and the
heat pump will operate unl the water temperature rises to the set temperature or the next command is received.