EDM SYSHP MINI SPLIT TANK
5
1.2 System Conguraons
It can be congured to run with the electric heater either enabled or disabled and can also be used in conjuncon with an
auxiliary heat source such as a boiler.
The chosen conguraon aects the size of heat pump that is required. Three typical conguraons are described below.
Conguraon 1: Heat pump only
▪ The heat pump covers the required capacity and no extra heang capacity is necessary.
▪ Requires selecon of larger capacity heat pump and implies higher inial investment.
▪ Ideal for new construcon in projects where energy eciency is paramount.
Conguraon 2: Heat pump and backup electric heater (Hydro module with water tank is standard with 3kW backup electric
heater)
▪ Heat pump covers the required capacity unl the ambient temperature drops below the point at which the heat pump
is able to provide sucient capacity. When the ambient temperature is below this equilibrium point, the backup electric
heater supplies the required addional heang capacity.
▪ Best balance between inial investment and running costs, results in lowest lifecycle cost.
▪ Ideal for new construcon.
Conguraon 3: Heat pump conjuncon with auxiliary heat source
▪ Heat pump covers the required capacity unl the ambient temperature drops below the point at which the heat pump is
able to provide sucient capacity. When the ambient temperature is below this equilibrium point, depending on the system
sengs, either the auxiliary heat source supplies the required addional heang capacity or the heat pump does not run and
the auxiliary heat source covers the required capacity.
▪ Enables selecon of lower capacity heat pump.
▪ Ideal for refurbishments and upgrades.
System conguraons
Conguraon 1
Conguraon 2
Conguraon 3
Heat pump capacity
Required capacity
Ambient temperature
Highest temperature
(No more heang)
Lowest temperature
(Design temperature)
Equilibrium points
Capacity