EDM SYSHP MINI SPLIT TANK
56
Abreviaons:
T4: Outdoor ambient temperature
IBH: Backup electric heater
1.10 OTHER HEATING SOURCE Menu
1.10.1 OTHER HEATING SOURCE menu overview
MENU > FOR SERVICEMAN > OTHER HEATING SOURCE
OTHER HEATING SOURCE menu
T4_IBH_ON
Abreviaons:
AHS: Addional heang source
T4: Outdoor ambient temperature
In OTHER HEATING SOURCE the following parameters should be set. Backup electric heater is oponal.
dT1_IBH_ON sets the temperature dierence between the heat pump’s leaving water set temperature (T1S) and the heat pump’s
leaving water temperature (T1) above which the backup electric heater heang element(s) are on. When T1S - T1 ≥ dT1_IBH_ON
the backup electric heater is on (on models where the backup electric heater has a simple on/o control funcon).
t_IBH_DELAY sets the delay between the compressor starng and the backup electric heater being turned on.
T4_IBH_ON sets the ambient temperature below which the backup
electric heater is used. If the ambient temperature is above T4_
IBH_ON, the backup electric heater is not used. The relaonship
between operaon of the backup heater and the ambient is shown
on right.
dT1_ASH_ON sets the temperature dierence between the heat pump’s leaving water set temperature (T1S) and the heat pump’s
leaving water temperature (T1) above which the addional heang source is on. When T1S - T1 ≥ dT1_AHS_ON the addional
heang source is on.
t_ASH_DELAY sets the delay between the compressor starng and the addional heang source being turned on.
T4_AHS_ON sets the ambient temperature below which the addional heang source is used. If the ambient temperature is
above T4_ASH_ON, the addional heang source is not used. The relaonship between operaon of the addional heang
source and the ambient is shown in the picture below.
Heat mode by
IBH only
Heat mode by heat
pump and IBH
Heat mode by
heat pump
T4_AHS_ON
Heat mode
by AHS only
Heat mode by heat
pump and AHS
Heat mode
by heat pump
IBH LOCATE means IBH is installed for pipe heang.
P_IBH1, P_IBH2 set heang capacity of IBH and P_TBH sets heang capacity of TBH, which are used for energy consumpon
stascs.