EDM SYSHP MINI SPLIT TANK
55
If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will be
displayed. In this case, the seng value of zone 1 is T1S, the seng value of zone 2 is T1S2. (The corresponding TIS2 is calculated
according to the climate related curves.)
Homepage (zone 1) Addion page (zone 2)
(Double zone is eecve)
Set DOUBLE ZONE to YES and set ROOM TEMP. to NON; Set WATER FLOW TEMP. to YES or NON
Set DOUBLE ZONE and ROOM TEMP. to YES; Set WATER FLOW TEMP. to YES or NON
Homepage (zone 1) Addion page (zone 2)
1.9 ROOM THERMOSTAT Menu
MENU > FOR SERVICEMAN > ROOM THERMOSTAT
As an alternave to controlling space heang/cooling modes according to the
Heat Pump Split unit’s leaving water temperature and/or the room temperature
detected by the temperature sensor in the Heat Pump Split user interface,
separate room thermostat can be installed and used to control space heang/
cooling modes.
In ROOM THERMOSTAT the following parameters should be set.
ROOM THERMOSTAT sets whether or not room thermostats are installed. For installaons with room thermostats, select YES. For
installaons without room thermostats, select NON.
ROOM THERMOSTAT = NON: No room thermostat.
ROOM THERMOSTAT = MODE SET: Room thermostat can control heang and cooling individually.
ROOM THERMOSTAT=ONE ZONE: Room thermostat provides the switch signal to unit.
ROOM THERMOSTAT=DOUBLE ZONE: Indoor unit is connected with two room thermostat.
ROOM THERMOSTAT menu