EDM SYSHP MINI SPLIT TANK

53
t_INTERVAL_H sets the heang mode compressor re-start delay. When the compressor stops running, it will not re-start unl
at least t_INTERVAL_H minutes have elapsed.
T1SetH1 sets the temperature 1 of automac seng curve for heang mode.
T1SetH2 sets the temperature 2 of automac seng curve for heang mode.
T4H1 sets the ambient temperature 1 of automac seng curve for heang mode.
T4H2 sets the ambient temperature 2 of automac seng curve for heang mode.
ZONE1 H-EMISSION sets the emission type for heang mode.
ZONE2 H-EMISSION sets the emission type for heang mode.
1.7 AUTO MODE SETTING Menu
MENU > FOR SERVICEMAN > AUTO MODE SETTING
In AUTO MODE SETTING the following parameters should be set.
T4AUTOCMIN sets the ambient temperature below which the heat pump
will not provide chilled water for space cooling in auto mode.
T4AUTOHMAX sets the ambient temperature above which the heat pump
will not provide heated water for space heang in auto mode.
T4AUTOCMAX, T4AUTOCMIN
Abreviaons:
HP: Heat pump
AHS: Addional heang source
IBH: Backup electric heater
T4CMAX: The ambient temperature above which the heat pump will not operate in cooling mode.
T4HMIN: The ambient temperature below which the heat pump will not operate in heang mode.
AUTO MODE SETTING menu
COOL
OFF OFF
Heat mode by
IBH or AHS
Heat mode by
heat pump