EDM SYSHP MINI SPLIT TANK

52
T4C1 sets the ambient temperature 1 of automac seng curve for cooling mode.
T4C2 sets the ambient temperature 2 of automac seng curve for cooling mode.
ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode.
ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode.
1.6 HEAT MODE SETTING Menu
MENU > FOR SERVICEMAN > HEAT MODE SETTING
HEAT MODE SETTING menu
T4HMAX, T4HMIN
Abreviaons:
T4: Outdoor ambient temperature
dTSH
Note:
Only when ROOM TEMP is enabled will this funcon
be available
In HEAT MODE SETTING the following parameters should be set.
HEAT MODE enables or disables heang mode.
t_T4_FRESH_H sets the refresh me of heang model climate temperature curve.
T4HMAX sets the ambient temperature above which the heat pump will not
operate in heang mode. The highest value that T4HMAX can take is 35°C, which
is the heang mode upper ambient temperature operang limit of the heat pump.
T4HMIN sets the ambient temperature below which the heat pump will not
operate in heang mode. The lowest value that T4CMIN can take is -25°C, which
is the heang mode lower ambient temperature operang limit of the heat pump.
dT1SH sets the temperature dierence between the heat pump leaving water
temperature (T1) and the heat pump leaving water set temperature (T1S) above
which the heat pump provides heated water to the space heang terminals.
dTSH sets the temperature dierence between the actual room temperature (Ta)
and set room temperature (TS) above which the heat pump provides heated water
to the space heang terminals. When TS Ta dTSH the heat pump provides
heated water to the space heang terminals and when Ta TS the heat pump
does not provide heated water to the space heang terminals. Refer to Figure
3-8.23. dTSH is only relevant if YES is selected for ROOM TEMP in the TEMP. TYPE
SETTING menu. Refer to Part 3, 8.8 “TEMP. TYPE SETTING Menu”.
OFF
HEAT
OFF
HEAT
OFF