EDM SYSHP MINI SPLIT TANK
15
Note:
(1)According to EN16147/2017;EU No:811/2013
(2)According to EN14511/2018; EN14825/2018; EU No:811/2013
(3)Sound power in heang mode, measured according to the EN 12102 under condions of the EN 14825
Drain connecon DN32
Outdoor unit sound Power Level(3) dB 56 58 59 60
Ambient
temperature
range
Heang °C
-25~35
Cooling °C
-5~43
Domesc hot water °C
-25~43
Indoor
Unit
Model
Power supply V/Ph/Hz 220-240/1/50
Rated input W 3095
Rated current A 13.5
DHW Tank
Type Stainless steel
Material - SUS 316L
Water Volume l 240
Maximum water
temperature(Disinfecon
mode)
°C 70
Maximum water pressure
limit
bar 10
Insulaon Material - Polyurethane (Cyclopentane)
Insulaon Thickness mm 45
Heat Exchanger Plate heat exchanger
Backup E-heater
Standard mounted kW 3
Capacity steps 1
Water Pump
Type DC-inventer
Max. head m 9
Expansion vessel Volume L 8
Water Piping
connecon
Water circuit
Inlet
R1”
Outlet
DHW tank water circuit
Cold Inlet
R3/4”
Hot Outlet
Recirculaon
Unit dimension (W×H×D) mm 600*600*1943
Packing dimension (W×H×D) mm 730*730*2180
Net/Gross weight kg 157 / 178
Ambient temperature range °C
5~35
LWT seng
range
Heang °C
25~65
Cooling °C
5~25
Domesc hot water °C
30~60
Indoor unit sound Power Level(3) dB 38 40