OM SYSHP MINI SPLIT
Parameter setting 2
BIT15
BIT14
BIT13
BIT12
BIT11
BIT10
BIT9
Reserved
BIT8
Define the port,
0=remote ON/OFF; 1=DHW heater
BIT7
Smart grid, 0=NON; 1=YES
BIT6:
Enable or disable the Tw2, 0=NON ; 1=YES
BIT5:
Setting the high/low temperature of cooling
mode T1S
BIT4:
Setting the high/low temperature of heating
mode T1S
BIT3:
Double zone setting is valid
BIT2:
Reserved
BIT1:
Reserved
BIT0:
Reserved
dT5_On
dT1S5
T_Interval_DHW
T4DHWmax
T4DHWmin
t_TBH_delay
dT5_TBH_off
T4_TBH_on
T5s_DI
211 (PLC:40212)
212 (PLC: 40213)
213 (PLC: 40214)
214 (PLC: 40215)
215 (PLC: 40216)
216 (PLC: 40217)
217 (PLC: 40218)
218 (PLC: 40219)
219 (PLC: 40220)
220 (PLC: 40221)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 10°C, range: 5~40°C, setting interval: 1°C
Default setting: 5 min, range: 5~30 min, setting interval: 1 min
Default setting: 43°C, range: 35~43°C, setting interval: 1°C
Default setting: -10°C, range: -25~5°C, setting interval: 1°C
Default setting: 30 min, range: 0~240 min, setting interval: 5 min
Default setting: 5°C, range: 0~10°C, setting interval: 1°C
Default setting: 5°C, range: -5~20°C, setting interval: 1°C
Temperature of the disinfection water tank, range: 60~70°C, default setting: 65°C
55