T1SetC1 sets the temperature 1 of automac seng curve for cooling mode.
T1SetC2 sets the temperature 2 of automac seng curve for cooling mode.
T4C1 sets the ambient temperature 1 of automac seng curve for cooling mode.
T4C2 sets the ambient temperature 2 of automac seng curve for cooling mode.
ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode.
ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode.
8.6 HEAT MODE SETTING Menu
MENU > FOR SERVICEMAN > HEAT MODE SETTING
Figure 3-8.14: HEAT MODE SETTING menu
Figure 3-8.15: T4HMAX, T4HMIN
Abreviaons:
T4: Outdoor ambient temperature
Figure 3-8.16: dTSH
Note:
Only when ROOM TEMP is enabled will this funcon
be available
In HEAT MODE SETTING the following parameters should be set.
HEAT MODE enables or disables heang mode.
t_T4_FRESH_H sets the refresh me of heang model climate temperature curve.
T4HMAX sets the ambient temperature above which the heat pump will not
operate in heang mode. The highest value that T4HMAX can take is 35°C, which
is the heang mode upper ambient temperature operang limit of the heat pump.
Refer to Figure 3-8.15.
T4HMIN sets the ambient temperature below which the heat pump will not
operate in heang mode. The lowest value that T4CMIN can take is -25°C, which
is the heang mode lower ambient temperature operang limit of the heat pump.
Refer to Figure 3-8.16.
dT1SH sets the temperature dierence between the heat pump leaving water
temperature (T1) and the heat pump leaving water set temperature (T1S) above
which the heat pump provides heated water to the space heang terminals.
OFF
HEAT
OFF
HEAT
OFF