Calculate condioned surface area
Select the heat emiers (type, quanty, water temperature and heat load)
Step 2: System conguraon
Decide whether to include AHS and set AHS’ s switching temperature
Decide whether backup electric heater is enabled or disabled
Step 3: Selecon of outdoor units
Determine required total heat load on outdoor units
Set capacity safety factor
Select power supply
Provisionally select the heat pump unit capacity based on nominal capacity
Correct capacity of the outdoor units for the following items:
Outdoor air temperature / Outdoor humidity / Water outlet temperature
1
/
Altude / An-freeze uid
Heat pump Split system
selecon is complete
4 System Design and Unit Selecon
4.1 Selecon procedure
Step 1: Total heat load calculaon
Is corrected Heat Pump Split unit capacity ≥ Required total heat load on outdoor
units
2
Yes
No
Select a larger model or enable
backup electric heater operaon
Notes:
1. If the required water temperatures of the heat emiers are not all the same, the Heat Pump Splits outlet water temperature seng should be set at the
highest of the heat emier required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor
units capacity table, calculate the corrected capacity by interpolaon.
2. If the outdoor unit selecon is to be based on total heang load and total cooling load, select Split units which sasfy both total heang and cooling load
requirements.