EDM SYSHP MINI SPLIT 06 16
Table Of Contents
- CONTENTS
- CONTENTS
- 1.1 System Schematic
- 1.2 System Configurations
- 2 Unit Capacities
- 2.1 Outdoor unit
- 3 Nomenclature
- 3.1 Outdoor unit
- 3.2 Hydronic box
- 4 System Design and Unit Selection
- 4.1 Selection procedure
- 4.2 M thermal Leaving Water Temperature (LWT) Selection
- 5 Typical Applications
- 5.1 Space Heating Only
- 5.2 Space Heating and Domestic Hot Water
- 5.3 Space Heating, Space Cooling and Domestic Hot Water
- 5.4 Space Heating and Domestic Hot Water (Bivalent)
- 5.4.2 Auxiliary heat source provides space heating and domestic hot water
- 5.5 Space Heating Through Floor Heating Loops and Radiators
- 5.6 Space Heating, Space Cooling and Domestic Hot Water Compatible with Solar Water Heater
- Part 2 Engineering Data
- 1.1 Outdoor Unit
- 1.2 Hydronic Box
- 2 Dimensions and Center of Gravity
- 2.1 Outdoor Unit
- 2.2 Hydronic Box
- 3.1 Outdoor Unit
- 4 Wiring Diagrams
- 4.1 Outdoor Unit
- 4.2 Hydronic Box
- 5 Capactiy Tables
- 5.2 Cooling Capacity Tables (Test standard:EN14511)
- 7 Hydronic Performance
- 8.1 Overall
- 8.2 Octave Band Levels
- 9.1 Outdoor Unit
- 1.1 Notes for Installers Boxes
- 2 Installation
- 2.1 Acceptance and Unpacking
- 2.3 Outdoor unit
- 1
- 1.1
- 1.2
- 1.3
- 1.4
- 1.5
- 2.4 Hydronic box
- 3 Refrigerant Pipework
- 3.1 Permitted Piping Length and Level Difference
- 3.3 Procedure and Principles
- 3.4 Storing Copper Piping
- 3.8 Pipe Flushing
- 3.9 Gastightness Test
- 4 Water Pipework
- 4.1 Water Circuit Checks
- 4.2 Water volume and sizing expansion vessels
- 4.3 Water Circuit Connection
- 4.4 Water Circuit Anti-freeze Protection
- 5.1 General
- 5.4 Wiring Overview
- 8.1 Introduction
- 8.2 Menu Structure
- 8.11 HOLIDAY AWAY SETTING Menu
- 8.14 TEST RUN
- 8.15 SPECIAL FUNCTION
- 8.16 AUTO RESTART
- 8.20 HMI ADDRESS SET
- 9 Operation parameter
- 10 Network Configuration Guidelines
- 10.1 Install APP
- 10.2 Sign in
- 10.3 Add device and login to home Wi-Fi
- 10.4 Wired Controller Setting
- 10.4.2 Finishing up
- 11 USB Function Guidelines
- 11.1 Parameters setting transfer between wired controllers
- 11.2 Convenient program upgrade for unit
- 12 Climate Related Curves
- 13 Error Code Table
- Part 1 General Information
- Part 2 Engineering Data
- Part 3
- Installation and Field Settings
- 1 Air-to-Water HP Split System
- 2 Unit Capacities
- 3 Nomenclature
- 4 System Design and Unit Selection
- 5 Typical Applications
- 1 Specifications
- 3 Piping Diagrams
- 4 Wiring Diagrams
- 5 Capactiy Tables
- 6 Operating Limits
- 7 Hydronic Performance
- 8 Sound Levels
- 9 Accessories
- 1 Preface to Part 3
- 3 Refrigerant Pipework
- 4 Water Pipework
- 6 DIP Switch Settings
- 7 Internal Circulation Pump
- 8 User Interface Field Settings
- 9 Operation parameter
- 10 Network Configuration Guidelines
- 11 USB Function Guidelines
- 12 Climate Related Curves
- 13 Error Code Table
90
Abreviaons:
T1: Heat pump leaving water temperature
T1S: Heat pump leaving water set temperature
Figure 3-8.10: COOL MODE SETTING menu
Figure 3-8.11: T4CMAX, T4CMIN
Abreviaons:
T4: Outdoor ambient temperature
Figure 3-8.12: dT1SC
Figure 3-8.13: dTSC
PUMP RUNNING TIME sets the length of me the pump runs for at each of the user-specied start mes on the DHW PUMP tab
on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled.
DHW PUMP DI RUN sets wether or not the DHW pump (eld supply) operates during the disinfecon mode.
8.5 COOL MODE SETTING Menu
MENU > FOR SERVICEMAN > COOL MODE SETTING
In COOL MODE SETTING the following parameters should be set.
COOL MODE enables or disables cooling mode. For installaons with space cooling
terminals, select YES to enable cooling mode. For installaons without space cooling
terminals, select NON to disable cooling mode.
t_T4_FRESH_C sets the refresh me of cooling mode climate temperature curve.
T4CMAX sets the ambient temperature above which the heat pump will not operate
in cooling mode. The highest value that T4CMAX can take is 46°C, which is the cooling
mode upper ambient temperature operang limit of the heat pump. Refer to Figure
3-8.11.
T4CMIN sets the ambient temperature below which the heat pump will not operate in
cooling mode. The lowest value that T4CMIN can take is -5°C, which is the cooling mode
lower ambient temperature operang limit of the heat pump. Refer to Figure 3-8.12.
dT1SC sets the minimum temperature dierence between the heat pump leaving water
temperature (T1) and the heat pump leaving water set temperature (T1S) at which the
heat pump provides chilled water to the space cooling terminals. When T1 – T1S ≥
dT1SC the heat pump provides chilled water to the space cooling terminals and when
T1 ≤ T1S the heat pump does not provide chilled water to the space cooling terminals.
dTSC sets the temperature dierence between the actual room temperature (Ta) and
set room temperature (TS) above which the heat pump provides chilled water to the
space cooling terminals. When Ta – TS ≥ dTSC the heat pump provides chilled water to
the space cooling terminals and when Ta ≤ TS the heat pump does not provide chilled
water to the space cooling terminals. Refer to Figure 3-8.18. dTSC is only applicable if
YES is selected for ROOM TEMP in the TEMP. TYPE SETTING menu. Refer to Part 3 8.8
“TEMP. TYPE SETTING Menu”.
t_INTERVAL_C sets the cooling mode compressor re-start delay. When the compressor
stops running, it will not re-start unl at least t_INTERVAL_C minutes have elapsed.
OFF
COOL OFF
OFF
COOL
OFF
COOL