Figure 3-8.43: Preheang for oor screens
During the oor drying up operaon all buons except OK are inacvated. To exit the oor
drying up operaon, press OK and then select YES when prompted.
Note: In the event of a heat pump malfuncon, oor drying up mode will connue if a
backup electric heater and/or addional heang source is available and congured to
support space heang mode.
Figure 3-8.44: FLOOR DRYING UP menu
Figure 3-8.46:
FLOOR DRYING UP screen
8.15.3 FLOOR DRYING UP
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR
DRYING UP
For newly-installed under-oor heang systems, oor drying
up mode can be used to remove moisture from the oor slab
and suboor to prevent warping or rupture of the oor during
oor heang operaon. There are three phases to the oor
drying up operaon:
Phase 1: gradual temperature increase from a starng point of 25°C to the peak temperature
Phase 2: maintain peak temperature
Phase 3: gradual temperature decrease from the peak temperature to 45°C
t_DRYUP sets the duraon of Phase 1.
t_HIGHPEAK sets the duraon of Phase 2.
t_DRYDOWN is the duraon of Phase 3.
T_DRYPEAK sets the heat pump’s leaving water set temperature for Phase 2.
START TIME sets the oor drying up operaon start me.
START DATE sets the oor drying up operaon start date.
The heat pump’s leaving water set temperature during the oor drying up operaon is illustrated in Figure 3-8.45.
Figure 3-8.45: FLOOR DRYING UP sengs
Time