SYSVRF2 224 280 AIR EVO A HP R IM
5
NOTE
Size of main pipe and corresponding branch joint and branch
header
Table 4-2
Select refrigerant pipe
Fig. 4-3
The unit body
Affiliated heat pump belt
Site pipe side
Cut from upward
4.3 Heat Insulation
Do the heat insulation to the pipes of air side and liquid side
separately. The temperature of the pipes of air side and liquid side
when cooling, for avoiding condensation please do the heat
insulation fully.
The air side pipe should use closed cell foamed insulation
material, which the fire-retardant is B1 grade and the heat
resistance over 120°C.
When the external diameter of copper pipe≤Φ12.7mm, the
thickness of the insulating layer at least more than 15mm;
When the external diameter of copper pipe≥Φ15.9mm, the
thickness of the insulating layer at least more than 20mm.
Please use attached heat-insulating materials do the heat
insulation without clearance for the connecting parts of the indoor
unit pipes.
Fig. 4-2
Check point of outdoor unit
Check point of indoor unit
pipe definition pipe connect position
The pipe between outdoor unit to the
first branch of indoor unit.
The main pipes of
indoor unit
code
Indoor unit branch
pipes components
L2~L5
L1
a,b,c,
d,e,f
A,B,C,
D,E
The first connect methond
NOTE
4.4 Confirmation for the diameters of indoor
unit connecting pipes
The straight distance between copper pipe turning and the contig-
uous branch pipe is at least 0.5m;
The straight distance between the contiguous branchpipes is at
least 0.5m;
The straight distance which the branch pipes connected to the
indoor unit is at least 0.5m;
4.4 Connecting method
main pipe
The branch pipes
of indoor unit
The pipe after the first branch do not
direct connect with the indoor unit.
The pipe after the branch connect with
the indoor unit.
The pipes connect with the main pipe、
the branch pipe and the the main pipe
of indoor unit.
The first Line Branch Pipe
Outdoor Unit
The first Line Branch Pipe
Outdoor Unit(Take Model 280 for example)
The second connect methond
intdoor Units
Fig. 4-4
Fig. 4-5
The distance between the first branch to the last indoor unit is
more than 15m,choose the second connect methond.
The pipe between the indoor unit to the closest branch must less
than 15m.
4.5 Confirmation for the diameters of outdoor
unit connecting pipes
D
C
A
B
a
b
c
e
f
d
L1
L2
L3
L4
L5
A
B
C
D
E
N1
(56)
N
3
(45)
N
5
(45)
N
6
(56)
N
2
(56)
N
4
(45)
A
B
D
E
C
a
b
c
e
f
d
L1
L2
L5
L3
L4
1) R410A Indoor unit connecting pipes diameters 4-3。
2) Example 1:In the Fig.4-5,The downstream inner units of the
L4,and its total capacity is 45×2=90,refers to the Table 4.4,the
air/liquid side of L4 is:Φ15.9/Φ9.5。
R410A Indoor unit connecting pipes diameters
Table 4-3
A<166
166≤A<230
Capacity of the
downstream
indoor unit
Main pipe size (mm)
Air pipe Liquid pipe
Φ15.9
Φ9.5
Φ9.5
Applicable
manifold
FQZHN-01D
FQZHN-01D
Φ19.1
230≤A<330
330≤A<470
Φ9.5 FQZHN-02DΦ22.2
Φ12.7 FQZHN-03DΦ25.4
Gas side
(mm)
Liquid si-
de
(mm)
20-28KW
Φ22.2 Φ9.5 Φ25.4
Φ12.7
Main pipe size when the tot-
al equivalent piping length
of liquid + gas side is <90m
R410A outdoor unit connecting pipes diameters
Total capa-
ctiy of The
outdoor
units
Table 4-4
Main pipe size when the tot-
al equivalent piping length
of liquid + gas side is ≥90m
Gas side
(mm)
Liquid si-
de
(mm)
The first Line
Branch Pipe
The first Line
Branch Pipe
FQZHN-02D
FQZHN-03D
33.5KW
Φ25.4
Φ12.7
FQZHN-03D
Φ25.4 Φ12.7
FQZHN-03D