SYSVRF 080 120 AIR EVO C HP Q IM20210526 082925148

16
Heating mode:
Item Symbol Value Unit Item Symbol Value Unit
Rated heating
capacity
P
rated,h
13.96 kW
Seasonal space heating
energy efficiency
η
s,h
169.8 %
T
j
=-7
P
dh
7.12 kW
T
j
=-7
COP
d
3.01 -
T
j
=+2
P
dh
5.06 kW
T
j
=+2
COP
d
3.99 -
T
j
=+7
P
dh
3.34 kW
T
j
=+7
COP
d
6.01 -
T
j
=+12
P
dh
3.47 kW
T
j
=+12
COP
d
7.34 -
T
biv
=bivalent
temperature
P
dh
7.90 kW
T
biv
=bivalent temperature
COP
d
3.01 -
T
OL
=operation
temperature
P
dh
7.12 kW
T
OL
=operation temperature
COP
d
1.84 -
Bivalent
temperature
T
biv
-7
Degradation co-
efficient for
heat pumps(**)
C
dh
0.25 -
Off mode
P
OFF
0.017 kW
Back-up heating capacity(*)
elbu 1.82 kW
Thermosat-off
mode
P
TO
0.011 kW Type of energy input
Crankcase heater
mode
P
CK
0.009 kW Standby mode
P
SB
0.017 kW
Capacity control
For air-to-air heat
pump:air flow rate,outdoor
measured
- 5000
m
3
/h
Sound power
level,outdoor
L
WA
70 d B
GWP of the
refrigerant
2088
kg CO
2
eq
(100years)
Contact details
(**)If Cdh is not dete
rmined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and performance data may be obtained on the basis of
performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
If applicable:driver of compressor:electric motor
Parameters shall be declared for the anerage heating season,parameters for the warmer and colder heating seasoms are optional
Declared heating capacity for part load at indoor
teperature 20 and outdoor temperatures
T
j
Declared coefficient of performance or gas utilisation
efficiency/auxiliary energy factor for part load at given
outdoor temperatures
T
j
Power consumption in modes other than "active mode" Supplementary heater
Other
items
variable
(*)
Information requirements for air-to-air conditioners
Model(s): SYSVRF 120 AIR EVO C HP Q;
Test matching indoor units form, non-duct: SYSVRF CASSETTE 36 Q + SYSVRF CASSETTE 28 Q*
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no