HAWAIR Engineering Data Manual (EDM HAW S 2GB)
Hawair
3
Hawair 2-pipe - With IR - With valve
Hawair HAW007 HAW009 HAW018 HAW022
capacities
Total cooling capacity (1) - LS W - 960 - 2390
Total cooling capacity (1) - MS W - 1200 - 2250
Total cooling capacity (1) - HS W - 1500 - 2810
Sensible capacity - LS W - 680 - 1850
Sensible capacity - MS W - 960 - 1540
Sensible capacity - HS W - 1120 - 2030
Water pressure drop - LS kPa - 31.5 - 84.3
Water pressure drop - MS kPa - 37.4 - 96.3
Water pressure drop - HS kPa - 44 - 111
Heating capacity (2) - LS W - 1250 - 3020
Heating capacity (2) - MS W - 1750 - 2850
Heating capacity (2) - HS W - 1980 - 3620
sound levels
Sound power level - LS dB(A) - 49 - 58
Sound power level - MS dB(A) - 52 - 61
Sound power level - HS dB(A) - 56 - 66
Sound pressure level (3) - LS dB(A) - 32 - 39
Sound pressure level (3) - MS dB(A) - 36 - 42
Sound pressure level (3) - HS dB(A) - 42 - 46
NR (3) - LS dB(A) - 27 - 34
NR (3) - MS dB(A) - 31 - 37
NR (3) - HS dB(A) - 37 - 41
ventilation
Number - 1 - 1
Air flow - LS rpm / m3/h - 900 / 246.4 - 1050 / 490
Air flow - MS rpm / m3/h - 1070 / 323 - 1200 / 560
Air flow - HS rpm / m3/h - 1260 / 390.6 - 1380 / 705
electrical characteristics
Power supply V/Ph/Hz 230V / 1~ / 50Hz
Consumption - LS W - 36 - 46
Consumption - MS W - 42 - 52
Consumption - HS W - 50 - 60
FCEER - E - E
FCCOP - E - E
water connection
Type Gas female
Coupling inch 1/2"
dimensions
Length x Width x Height mm - 845 x 275 x 180 - 940 x 298 x 200
weight
Weight kg - 11 - 13
(1) According to Eurovent : Air = 27 °C dry bulb / 19 °C wet bulb - Water = 7 °C / 12 °C.
(2) According to Eurovent : Air = 20 °C, same ow as in cooling mode.
(3) Sound pressure levels considering a room having a volume of 100 m3, with a reverberation time of 0.5 seconds and a distance of 1 meter.
Technical Data (continued)