The BACnet device for each indoor unit provides the following objects:
Object ID
Room temperature (unit: °C)
Error Code (see 4-3)
Object Name
Current Value Description
Indicates the error status of the indoor unit:
0 - No error; 1 - Error
0 - Unlock remote control; 1 - Lock remote
control
4
The following describes the abbreviations used for different object types:
Object Type Abbreviation
4-1 BACnet Objects in Indoor Units
4. Object List
ON/OFF Settings for Indoor Units
0 - OFF; 1 - ON
When On is set, the operating mode, fan speed
and temperature settings sent to the unit are
based on what have been recorded in the last
operation of the indoor unit. If the indoor unit is
in Off status when the gateway is initialized, the
default mode will be cooling with temperature at
24°C and fan speed set to low speed (1).
Analog Input AI
Analog Output AO
Analog Value AV
Binary Input
Binary Output
BI
BO
Binary Value BV
Multi-state Input
Multi-state Output
MI
MO
Multi-state Value MV
AI 1
AI 7
Room Temperature
Malfunction Code
R/W
R
R
BI 2 Alarm Indication R
BV 1 On/Off Setting RW
BV 4 Remote Control
Lock Setting
RW