SYS GW BACNET OM

Before use, you need to configure the device. To access the configuration page, start a browser
and enter the device IP address.
3-1 Date and Time Settings
You can set the date and time. The settings take effect immediately.
3-2 Security Settings
You can set the admin password. The settings take effect immediately.
The admin account is "admin", and the default password is "123456".
3-3 Network Settings
The default IP address of the Ethernet port is "192.168.1.8". You may ask the network
administrator to assign an IP address according to actual circumstances. Then, you can access
the configuration page to change the IP address of the gateway.
3-4 BACnet Settings
The BACnet network number is in the range of 2~254. You need to restart the device for the new
settings to take effect. Different gateways must have different BACnet network numbers, and the
same network number cannot be used for other devices. The rules to generate the BACnet
device instance number are as follows:
BACnet device instance number for indoor unit = (BACnet network number * 10000) + (Port
number * 1000) + (Indoor unit address);
BACnet device instance number for outdoor unit = (BACnet network number *10000) + (Port
number *1000) +100+ (Outdoor unit address)
485 port number: 0~3. For the 485 port near the network port, the number is 0.
Indoor unit address: 0~63; outdoor unit address: 0~31.
3-5 Reset IP Address
Before the device is powered on, connect ports 485A and 485B short. Then, restart the device.
The IP address is reset to 192.168.1.8.