4. Where there is a high salt content in the air. When exposed to
air with a high salt content, the mechanical parts will experience
accelerated ageing which will severely compromise the service
life of the unit.
5. Where there are major voltage fluctuations. Operating the unit
using a power supply system that has large voltage fluctuations
will reduce the service life of the electronic components, and
cause the unit's controller system to malfunction.
6. Where there is a risk of leakage of flammable gases. Examples
are sites that contain carbon fibres or combustible dust in the
air, or where there are volatile combustibles (such as diluent or
petrol). The above gases may cause explosion and fire.
7. Do not touch the fins of the heat exchanger as this may lead to
injury.
8. Some products use the PP packing belt. Do not pull or tug on
the PP packing belt when you transport the product. It will be
dangerous if the packing belt breaks.
9. Note the recycling requirements for nails, wood, carton and
other packaging materials. Do not discard these materials
directly as these may lead to bodily harm.
10. Tear up the packaging bag for recycling to prevent children from
playing with it, and leading to suffocation.
Accessories
2
Code
1
2
3
Note
Verify that the air conditioner includes the following accessories.
Qty
Appearance
Name
2. Insulation piping
4. Ring clamp for water discharge pipes
3. Water discharge hose
5. Brass nuts
6. Sponge
7. Display controller assembly
1
2
1
1
1
1
Function
1. Installation Manual for Indoor Unit
This manual
Included with 80-140 models only
1
Receive remote signals
8. Connecting wire
1
For insulation of piping connections
PVC pipe for
water discharge
Choose and purchase copper pipes that correspond
to the length and size calculated for the selected
model in the installation manual of the outdoor unit
and your actual project requirements.
Inner diameter, 25 mm.
The inner diameter is based on the diameter of the
copper and PVC pipes. The thickness of the pipe
casing is 10 mm or more. Increase the thickness of
the casing (20 mm or thicker) when the temperature
exceeds 30°C or the humidity exceeds RH80%.
To purchase based on actual
project requirements.
Use to connect indoor
refrigerant piping.
Use to discharge condensed
water from the indoor unit.
To purchase based on actual
project requirements.
To purchase based on actual
project requirements.
Protect piping from
condensation.
Name Appearance Dimensions Qty
Copper pipe
Insulation casing
for piping
Connect the drainage outlet of the indoor
unit to the PVC water piping.
To clamp the water discharge hose tightly
to the drainage outlet of the indoor unit.
For use in the installation works of
connecting piping
Accessories to purchase locally
For installation of indoor unit.
For installation of indoor unit.
Expansion hook
anchor
Mounting hook
M10
M10
4
5
To purchase based on actual
project requirements.
To purchase based on actual
project requirements.
Connect the wire controller
Tie
6
To purchase based on actual
project requirements.
Tie for connecting wire
To purchase based on actual
project requirements.
11.The appliance shall not be installed in the laundry.
When the product is used for comercial application. This
appliance is intended to be used by expert or trained users in
shops, in light industry and on farms, or for commercial use by lay
persons,the sound pressure level is below 70 dB(A).