SYSVRF2 DUCT IM

Fig.6-6
Fig.6-7
Fig.6-8
9
(Pa)
(Pa)
Model:80
0
20
40
60
80
100
120
750 850 950 1050 1150 1250 1350
10
20
30
40
50
60
70
80
90
100
LLL
LL
L
M
H
SH
POWER
Q(m
3
/h)
(Pa)
(Pa)
Model:90
0
20
40
60
80
100
120
750 850 950 1050 1150 1250 1350
10
20
30
40
50
60
70
80
90
100
LLL
LL
L
M
H
SH
POWER
Q(m
3
/h)
(Pa)
(Pa)
Model:112
0
20
40
60
80
100
120
1050 1150 1250 1350 1450 1550
10
20
30
40
50
60
70
80
90
100
LLL
LL
L
M
H
SH
POWER
Q(m
3
/h)
Fig.6-9
(Pa)
(Pa)
Model:140
0
20
40
60
80
100
120
140
160
1250 1350 1450 1550 1650 1750 1850 1950 2050
30
40
50
60
70
80
90
100
125
150
LLL
LL
L
M
H
SH
POWER
Q(m
3
/h)
Fig.6-10
Set proper external static pressure (ESP) according to the actual installation
conditions. Otherwise it may cause some problems.
ESP can be set through the DIP switch SW2 on the main board or the new
wired controller. Please refer to Part “8.3 DIP switch settings on main board”
for SW2 setting or the wired controller manual for wired controller setting.
If the connecting duct is long and the ESP setting is small, the airflow will
be very small, leading to poor performance.
If the connecting duct is short and the ESP setting is large, the airflow will
be very large, leading to higher operating noise and even water may be
blown out through the air outlet.
Four ESP can be set through DIP switch SW2.
Ten ESP can be set through the new wired controller.
Capacity ESP1 ESP2 ESP3 ESP4
2.2-7.1kW 10Pa 30Pa 50Pa
8-11.2kW 20Pa 40Pa 70Pa 100Pa
14kW 40Pa 70Pa
70Pa
100Pa 150Pa
Capacity 00 01 02 03 04 05 06 07 08 09
2.2-7. 1kW 0Pa 10Pa 20Pa 30Pa 40Pa 50Pa 60Pa 70Pa 70Pa 70Pa
8-11.2kW 10Pa 20Pa 30Pa 40Pa 50Pa 60Pa 70Pa 80Pa 90Pa 100Pa