7.4 Error codes
With the exception of a mode conflict error, contact your supplier or service engineer if any of the error codes listed in 
Table 7-3 are displayed on the unit's display panel. If the mode conflict error is displayed and persists, contact your 
supplier or service engineer. These errors should only be investigated by a professional technician. The descriptions are 
provided in this owner's manual for reference only.
Notes: 
 NO.
1
2
3
4
5
6
7
8
9
10
Display output
Four LED display Digital display
Mode conflict
Communication error between 
indoor and outdoor units
Indoor ambient temperature 
sensor error
Indoor heat exchanger mid-point 
temperature sensor error
Indoor heat exchanger outlet 
temperature sensor error
Fan error
EEPROM mismatch
Outdoor unit error
Water level error
The indoor unit has not been
assigned an address
Content
DEF./FAN LED 
flashes rapidly
TIMER LED flashes 
rapidly
OPERATION LED 
flashes rapidly
ALARM LED flashes 
slowly
OPERATION LED 
flashes rapidly
OPERATION LED 
flashes rapidly
TIMER LED flashes 
rapidly
DEF./FAN LED 
flashes rapidly
ALARM LED flashes 
slowly
OPERATION LED 
flashes rapidly
E0
FE
EE
Ed
E7
E6
E4
E3
E2
E1
Table.7-3
Error Code Table
Possible causes
Communicaon wires between
 indoor and outdoor units not 
connected properly.
Interference from high voltage 
wires or other sources of 
electromagnec radiaon.
Communicaon wire too long.
Damaged main PCB.
The indoor unit’s operang mode 
conflicts with that of the outdoor 
units.
Temperature sensor not 
connected properly or has 
malfunconed.
Damaged main PCB.
Fan stuck or blocked.
Fan motor not connected properly 
or has malfunconed.
Power supply abnormal.
Damaged main PCB.
Damaged main PCB.
Outdoor unit error.
Water level float stuck.
Water level switch not connected
 properly.
Damaged main PCB.
Drain pump has malfunconed.
Indoor unit has not been assigned 
an address.
EEV error
/
Eb
Line loosened or broken.
The electronic expansion valve 
in stuck.
Damaged main PCB.