Keep fastening the screws under the panel hooks until the
thickness of sealing sponges 1&2 between the body and
the panel's outlet has been reduced to about 4-6mm. The
edge of the panel should touch the ceiling well. (Refer to
Fig.5-12)
3
4
The fault described in Fig.5-13 can be caused if screws
are not tightly fastened
If the gap between the panel and ceiling still exists after
fastening the screws, the height of the indoor unit should
be adjusted. (Refer to Fig.5-14-left)
Modify the height of the indoor unit through the openings
on the panel's four corners, if lifting the indoor unit and the
drainage pipe is not influenced (Refer to Fig.5-14-right ).
Hang the air inlet grid on the panel. Then connect the
lead terminals for the swing motor and control box with
the corresponding terminals on the body.
Relocate the air inlet grid in the procedure in the reverse
order to install it.
Fig.5-14
Leakage
Dew
Swing motor installation cover
1
Hexagon nut
Ceiling
Horizontal adjustment
condensed water
Gaps are
not allowed
Ceiling
Body
Ceiling
Air plate
Panel
Panel foam 2
Panel sealing
sponge 1
Inlet air
Outlet air
Panel foam 1
Panel sealing
sponge 2
Panel sealing sponge 3
Steel rope
Drainage side
Swing motor side
Bolt, washer
Note: Please operate
according to the direction of
the arrow,or it can not be
disassembled when it is
necessary.
Steel rope
2
3
4
Guard of wire
(Protrusion 20mm)