Outdoor units electrical characteristics
Remark:
MCA: Min. Circuit Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Load Amps. (A)
OFM:Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW)
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
Maximum allowable voltage variation between phases is 2%.
2. Select wire size based on the value of MCA.
3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.
Outdoor unit power wire sizing and circuit breaker sizing selection should be done in accordance with the applicable legislation
based on below table.
Table 6-2
Voltage
(V)
Hz Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW FLA
(A)
System
Outdoor Unit Power Current Compressor OFM
10HP
12HP
14HP
16HP
18HP
22HP
24HP
26HP
28HP
30HP
32HP
20HP
25.2 30.9
-
10.6
0.56
6.3
440 35380~415 342
-
15.4
0.56
6.9
26.4 31.5440 35380~415 342
-
33.1 40.3
25.8
0.92
7.3
440342 45380~415
-
33.1 40.3
25.8
0.92
7.3
440 45380~415 342
-
40.8 59.3
10.114+13
440 70380~415 342
-
17+16
43.9 60.1 0.56+0.56
0.56+0.56
10.9
440 70380~415 342
-
19+18
47.9 60.1 0.56+0.56
10.9
440 70380~415 342
440 80380~415 342
-
0.92+0.92
22+30
66.9 72.5
14.9
440 80380~415 342
-
0.92+0.92
20+30
64.9 72.5
14.9
440 70380~415 342 0.92+0.9252.9 62.3
13.120+19.8
-
440 70380~415 342 0.92+0.9258.7 64.1
14.922+21.8
-
440 70380~415 342
-
48.4
17.4+16.6
0.92+0.92
13.1
62.3
24 35
-
0.56
6.3
380~415
50
50
50
50
50
50
50
50
50
50
50
50
50
342 440 30.9
10
8HP