IOM SYSPLIT MULTI EVO R32

Air Evacuation
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe
Length(m)
Air Purging
Method
Additional Refrigerant(R410A)
Less than
Standard pipe length x N
Vacuum Pump
N/A
More than
Standard pipe length x N
Vacuum Pump
Liquid Side: Ø 6.35 (Ø 1/4”)
(Total pipe length - pre-charge pipe lengthxN) x15g/m
Liquid Side: Ø 9.52 (Ø 3/8”)
(Total pipe length - pre-charge pipe lengthxN) x30g/m
Only for Australia models :
DO NOT
mix refrigerants types.
N=2(one-twin models),N=3(one-three models),N=4(one-four models),N=5(one-ve models).
Some systems require additional charging depending on pipe lengths. The standard pipe length
is 10m. The additional refrigerant to be charged can be calculated using the following formula:
Make sure to remove the additional refrigerant charge according to the rated volume (5m
refrigerant piping) when doing market or government verication test.