SYSPLIT WALL PRIME R32 PRODUCT FICHE

17
Seasonal efciency according to EN 14825.
The sound pressure value of the outdoor units is measured in free eld at a distance of 2 m. The sound pressure value of the indoor units is measured at 1 m from the front of the unit.
Nominal conditions
Indoor unit Outdoor unit Piping length Level difference
Cooling mode 27°C DB, 19°C WB 35°C DB 5 m 0 m
Heating mode 20°C DB, 19°C WB 7°C DB, 6°C WB 5 m 0 m
Hi-wall Inverter Split
|
Technical features
Model Indoor unit SYSPLIT WALL PRIME 09 INV HP Q PRIME 12 INV HP Q PRIME 18 INV HP Q PRIME 24 INV HP Q
Model Outdoor unit SYSPLIT WALL OUT 09 INV32 HP Q OUT 12 INV32 HP Q OUT 18 INV32 HP Q OUT 24 INV32 HP Q
Art. no. Indoor unit 315750 315806 315807 315808
Art. no. Outdoor unit 315809 315810 315811 315812
Refrigerant / Charged quantity kg R32 / 0,5 R32 / 0,5 R32 / 1,0 R32 / 1,6
Power supply V/Ph/Hz 220-240/1/50
Cooling capacity kW 2,64 ( 0,91-3,40) 3,52 (1,11-4,16) 5,28 (1,82-6,13) 7,03 (2,08-7,95)
Power consumption W 710 (100-1.240) 1.237 (130-1.580) 1.539 (140-2.360) 2.345 (160-2.960)
Operating current A 3,1 (0,4-5,4) 5,37 (0,5-6,9) 6,9 (0,6-10,3) 10,2 (0,7-13,3)
EER 3,72 2,85 3,43 3,00
SEER 6,2 6,1 7,1 6,1
Energy label cooling A++ A++ A++ A++
Heating capacity kW 2,93 (0,82-3,37) 3,81 (1,08-4,22) 5,57 (1,38~6,74) 7,33 (1,61-8,79)
Power consumption W 739 (120-1.200) 964 (100-1.580) 1.480 (200-2.410) 2.035 (260-3.140)
Operating current A 3,2 (0,5-5,2) 4,19 (0,4-6,9) 6,4 (0,9-10,5) 10,2 (1,1-13,3)
COP 3,96 3,95 3,76 3,60
SCOP (Warmer / Average) 4,9 / 4,0 4,6 / 4,0 5,2 / 4,0 5,0 / 4,0
Energy label (Warmer / Average) A++ / A+ A++ / A+ A+++ / A+ A++ / A+
Indoor unit
Air ow rate (H/M/L) m3/h 520/460/360 600/500/360 840/680/540 980/817/662
Indoor fan AC motor DC motor
Sound pressure level (H/M/L/S) dB(A) 40/30/26/21 40/34/26/22 44/37/30/25 44.5/42/34.5/28
Sound power level (H) dB(A) 53 53 55 59
Dimensions LxWxH mm 805x194x285 805x194x285 957x213x302 1.040x220x327
Packing LxWxH mm 870x270x360 870x270x360 1.035x295x380 1.120x405x310
Net/gross weight kg 7,5/9,7 7,5/9,7 10/13 12,3/15,8
Drain piping mm ODФ16 ODФ16 ODФ16 ODФ16
Outdoor unit
Compressor Rotary DC Inverter
Outdoor fan DC motor
Sound pressure level (H) dB(A) 44 48 44 50
Sound power level (H) dB(A) 61 65 61 67
Dimensions LxWxH mm 700x275x550 700x275x550 800x333x554 845x363x702
Packing LxWxH mm 815x325x615 815x325x615 920x390x615 965x395x765
Net/gross weight kg 22,7/25,2 22,7/25,2 34/36,7 51,5/54,5
Piping diameters
Liquid mm(inch) 6,35 (1/4") 6,35 (1/4") 6,35 (1/4") 9,52 (3/8")
Gas mm(inch) 9,52 (3/8") 9,52 (3/8") 12,7 (1/2") 15,9 (5/8")
Max. input current A 10 10 13,5 17,5
Maximum length of the line m 25 25 30 50
Maximum height difference m 10 10 20 25
Indoor temperature °C +17…+32 cooling / heating 0…+30
Outdoor temperature °C -15…+50 cooling / heating -15…+30