VRF AHU KIT4
Installation and Operating Manual
VRF-AHU Kit 9
2.3 Inspection and handling during delivery and assembly
■ Check the packaging for damage when it is delivered and report any damage immediately to
your sales partner.
■ Observe the following symbols and instructions on the packaging:
This way up: The pack must always be transported, folded and stored so that the arrows
always point upwards. Rolls, flaps, heavy tipping or edges as well as other forms of
treatment are to be omitted.
Fragile: Goods marked with this symbol have to be handled with care and must not be
overthrown or laced.
■ Ensure that the unit can be transported safely to the installation site.
■ If possible, transport the device only in its original packaging to the the installation site. Unpack
the unit immediately before installation.
■ Observe the weight of the unit. Do not lift or transport the unit alone or use a transport aid.
Observe the center of gravity of the device during transport and installation.
3 Scope of delivery and specifications
The VRF-AHU Kit is delivered with the following accessories. Check the delivery for
completeness. Unused accessories should be stored for future usage. In case of missing items
please contact your sales partner immediately.
Table 3-1
Casing
Metal
Dimension (h x w x d)
130 x 248 x 350 mm
Weight
approx 4.5 kg
Operation Temperature Range
-25 °C… +45 °C
Operation Humidity Range
40 - 90 %
Power Supply
230 VAC, 1 Phase, 50 Hz
Voltage Range
208 - 240 V
Recommended Fuse
16 A
Resistance class
IPX0
Max. operation pressure
42 bar
Packing list
Box body
1 piece
Box cover
1 piece
EVV
1 piece (built-in)
Temp sensor
2 pieces
Gland
4 pieces
Manual
1 piece