SYSPLIT CASSETTE R32 PRODUCT FICHE

|
29
Cassette Inverter High efciency Split
|
Technical features
Model Indoor unit SYSPLIT
CASSETTE 24
EVO HP Q
CASSETTE 36
EVO HP Q
CASSETTE 36
EVO HP Q
CASSETTE 48
EVO HP Q
CASSETTE 60
EVO HP Q
Model Outdoor unit SYSPLIT
OUTDOOR 24
EVO32 HP Q
OUTDOOR 36
EVO32 HP Q
OUTDOOR 36
EVO32 HP R
OUTDOOR 48
EVO32 HP R
OUTDOOR 60
EVO32 HP R
Model Panel unit SYSPANEL
CASSETTE
EVO SPLIT
CASSETTE
EVO SPLIT
CASSETTE
EVO SPLIT
CASSETTE
EVO SPLIT
CASSETTE
EVO SPLIT
Art. no. Indoor unit 315214 315215 315215 315216 315217
Art. no. Outdoor unit 315816 315866 315867 315868 315869
Art. no. Panel 314478 314478 314478 314478 314478
Refrigerant / Charged quantity kg R32 / 1,5 R32 / 2,4 R32 / 2,4 R32 / 2,8 R32 / 2,95
Power supply Indoor unit V/Ph/Hz
220-240/1/50-60
Power supply Outdoor unit V/Ph/Hz
220-240/1/50 or 60 380-415/
3+N
/50 or 60
Cooling capacity kW
7,03
(2,23-8,21)
10,55
(2,64-12,02)
10,55
(2,64-12,02)
14,0
(4,76-14,58)
15,8
(5,28-16,71)
Power consumption W
2.190
(480-2.850)
3.750
(660-4.500)
3.950
(660-4.500)
5.130
(1.174-5.602)
5.951
(1.147-6.682)
Operating current A
9,5
(2,1-12,4)
16,3
(2,9-19,6)
7,2
(1,2-8,2)
8,3
(1,8-9,26)
9,80
(1,8-11,0)
EER 3,21 2,81 2,67 2,73 2,66
SEER 6,1 6,1 6,1 6,1 6,1
Energy label cooling A++ A++ A++ A++ A++
Heating capacity kW
7,62
(2,43-8,65)
11,14
(2,93-13,19)
11,14
(2,93-13,19)
16,1
(3,93-16,77)
18,2
(4,4-19,34)
Power consumption W
2.050 (500-2.880) 2.960 (650-4.550) 3.000 (650-4.550) 5.050 (987-5.378) 6.036 (1.022-6.448)
Operating current A
8,9
(2,2-12,5)
12,9
(2,8-19,8)
5,5
(1,2-8,3)
8,2
(1,56-8,83)
9,9
(1,6-10,6)
COP 3,72 3,76 3,71 3,19 3,02
SCOP (Warmer / Average) 5,1 / 4,0 5,1 / 4,0 5,1 / 4,0 5,1 / 4,0 5,1 / 4,0
Energy label (Warmer / Average) A+++ / A+ A+++ / A+ A+++ / A+ A+++ / A+ A+++ / A+
Indoor Unit
Air ow rate (H/M/L) m
3
/h
1.378
/1.200/1.032
1.775
/1.620/1.438
1.775
/1.620/1.438
1.715
/1.568/1.381
1.970
/1.737/1.537
Indoor fan DC motor
Sound pressure level (H) dB(A) 47/43/40 52/49/46 52/49/46 52/50/49 53/50,5/48
Sound power level (H) dB(A) 59 61 62 65 65
Dimensions (Panel) LxWxH mm
840(950)x840(950)
x205(55)
840(950)x840(950)x245(55)
840(950)x840(950)
x287(55)
Packing (Panel) LxWxH mm
900(1.035)
x900(1.035)x225(90)
900(1.035)x900(1.035)x265(90)
900(1.035)x900(1.035)
x292(90)
Net/gross (Panel) weight kg
23(5)/
27(8)
27,5(5)/
31(8)
27,5(5)/
31(8)
29(5)/
32,7(8)
2 9 , 7 ( 5 ) /
33,4(8)
Drain piping ODФ25
Outdoor Unit
Compressor Rotary DC Inverter
Outdoor fan DC motor
Sound pressure level (H) dB(A) 49 51 51 55 57
Sound power level (H) dB(A) 66 68 68 72 74
Dimensions LxWxH mm 845x363x702 946x410x810 952x415x1.333
Packing LxWxH mm 965x395x765 1.090x500x875 1.095x495x1.480
Net/gross weight kg 66,8/72,6 66,8/73,4 81,5/87,0 106,7/119,9 111,3/124,3
Piping diameters
Liquid mm(inch) 9,52 (3/8") 9,52 (3/8") 9,52 (3/8") 9,52 (3/8") 9,52 (3/8")
Gas mm(inch) 15,9 (5/8") 15,9 (5/8") 15,9 (5/8") 15,9 (5/8") 15,9 (5/8")
Max. input current A 13,5 21,5 10,0 11,2 14,0
Maximum length of the line m 50 65 65 65 65
Maximum height difference m 25 30 30 30 30
Indoor temperature °C +17…+32 cooling / heating 0…+30
Outdoor temperature °C -15…+50 cooling / heating -20…+24
Seasonal efciency according to EN 14825. Seasonal efciency and energy labelling is not applicable to split systems with cooling capacity exceeding 12 kW.
The sound pressure value of the outdoor units is measured in free eld at a distance of 2 m. The sound pressure value of indoor units is measured at 1.4 m below the unit.
Twin combination - Indoor units operate simultaneously, with the same settings. The real capacity of the ststem depends on the capacity of the outdoor unit.
(1) 2x CASSETTE 18 with OUTDOOR 36; (2) 2x CASSETTE 24 with OUTDOOR 48; (3) 2x CASSETTE 30 with OUTDOOR 60; (4) 2x CASSETTE 36 with OUTDOOR 60.
Nominal conditions
Indoor unit Outdoor unit Piping length Level difference
Cooling mode 27°C DB, 19°C WB 35°C DB 5 m 0 m
Heating mode 20°C DB, 19°C WB 7°C DB, 6°C WB 5 m 0 m