SYSPLIT WALL EDGE R32 INSTALLATION MANUAL
 Page 29 
Air Evacuation
7
Preparations and Precautions
Air and foreign matter in the refrigerant circuit 
can cause abnormal rises in pressure, which 
can damage the air conditioner, reduce its 
efficiency, and cause injury. Use a vacuum pump 
and manifold gauge to evacuate the refrigerant 
circuit, removing any non-condensable gas and 
moisture from the system.
Evacuation should be performed upon initial 
installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
 
Check to make sure that both high-
pressure and low-pressure pipes between 
the indoor and outdoor units are 
connected properly in accordance with the 
Refrigerant Piping Connection section of 
this manual.
 
Check to make sure all wiring is connected 
properly.
Evacuation Instructions
Before using the manifold gauge and vacuum 
pump, read their operation manuals to familiarize 
yourself with how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure 
valve
Pressure hose / 
Charge hose
Charge hose
Vacuum
pump
Pressure gauge
Low pressure valve
1. 
Connect the charge hose of the manifold 
gauge to service port on the outdoor unit’s 
low pressure valve.
2. 
Connect another charge hose from the 
manifold gauge to the vacuum pump.
MC MC
Fig. 6.1
Air Evacuation