SYSPLIT WALL EDGE R32 INSTALLATION MANUAL
 Page 18 
Indoor Unit 
Installation
5.
Facing the back of the unit, remove the plastic 
panel on the bottom left-hand side.
6.  Feed the signal wire through this slot, from 
the back of the unit to the front.
7.  Facing the front of the unit, match the wire 
colors with the labels on the terminal block, 
connect the u-lug and and firmly screw each 
wire to its corresponding terminal.
 CAUTION
DO NOT MIX UP LIVE AND NULL WIRES
This is dangerous, and can cause the air 
conditioning unit to malfunction.
8. 
After checking to make sure every connection
is secure, use the cable clamp to fasten the 
signal cable to the unit. Screw the cable clamp 
down tightly.
9. 
Replace the wire cover on the front of the 
unit, and the plastic panel on the back.
 NOTE ABOUT WIRING
Step 7: Wrap piping and cables
Before passing the piping, drain hose, and the 
signal cable through the wall hole, you must 
bundle them together to save space, protect 
them, and insulate them.
1. 
Bundle the drain hose, refrigerant pipes, and 
signal cable according to Fig. 3.10. 
Indoor Unit
Space behind unit
Refrigerant piping
Drain hose
Signal wire
Insulation tape
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom 
of the bundle. Putting the drain hose at the 
top of the bundle can cause the drain pan 
to overflow, which can lead to fire or water 
damage.
DO NOT INTERTWINE SIGNAL CABLE WITH 
OTHER WIRES
While bundling these items together, do not 
intertwine or cross the signal cable with any 
other wiring.
2. 
Using adhesive vinyl tape, attach the drain 
hose to the underside of the refrigerant pipes.
3. 
Using insulation tape, wrap the signal wire, 
refrigerant pipes, and drain hose tightly 
together. Double-check that all items are 
bundled in accordance with Fig. 3.10. 
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends 
of the piping unwrapped. You need to access 
them to test for leaks at the end of the 
installation process (refer to Electrical Checks  
and Leak Checks section of this manual).
Step 8: Mount indoor unit
If you installed new connective piping to the 
outdoor unit, do the following:
1. 
If you have already passed the refrigerant 
piping through the hole in the wall, proceed 
to Step 4.
2. 
Otherwise, double-check that the ends of the 
refrigerant pipes are sealed to prevent dirt or 
foreign materials from entering the pipes.
3. 
Slowly pass the wrapped bundle of refrigerant 
pipes, drain hose, and signal wire through the 
hole in the wall.
4. 
Hook the top of the indoor unit on the upper 
hook of the mounting plate.
5. 
Check that unit is hooked firmly on mounting 
by applying slight pressure to the left and 
right-hand sides of the unit. The unit should 
not jiggle or shift.
6. 
Using even pressure, push down on the 
bottom half of the unit. Keep pushing down 
until the unit snaps onto the hooks along the 
bottom of the mounting plate.
7. 
Again, check that the unit is firmly mounted 
by applying slight pressure to the left and the 
right-hand sides of the unit.
Fig. 3.10
THE WIRING CONNECTION PROCESS MAY
DIFFER SLIGHTLY BETWEEN UNITS. 