SYSPLIT WALL EDGE R32 INSTALLATION MANUAL
 Page 17 
Indoor Unit 
Installation
Step 6: Connect signal cable
The signal cable enables communication between 
the indoor and outdoor units. You must first 
choose the right cable size before preparing it for 
connection.
Cable Types
• 
Indoor Power Cable
 (if applicable): 
H05VV-F or H05V2V2-F
• 
Outdoor Power Cable:
 H07RN-F
• 
Signal Cable: H07RN-F
Minimum Cross-Sectional Area of 
Power and Signal Cables
Other Regions
Rated Current of 
Appliance (A)
Nominal Cross-Sectional 
Area (mm²)
> 3 and ≤ 6 0.75
> 6 and ≤ 10 1
> 10 and ≤ 16 1.5
> 16 and ≤ 25 2.5
> 25 and ≤ 32 4
> 32 and ≤ 40 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal 
cable, fuse, and switch needed is determined 
by the maximum current of the unit. The 
maximum current is indicated on the nameplate 
located on the side panel of the unit. Refer to 
this nameplate to choose the right cable, fuse, 
or switch.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is 
designed with a fuse to provide overcurrent 
protection. The specifications of the fuse 
are printed on the circuit board, such as: 
Indoor unit: T5A/250VAC
Outdoor unit: 
T20A/250VAC(<=18000Btu/h units)
T30A/250VAC(>18000Btu/h units)
NOTE: The fuse is made of ceramic.
1. 
Prepare the cable for connection:
a. 
Using wire strippers, strip the rubber jacket 
from both ends of signal cable to reveal 
about 40mm (1.57in) of the wires inside.
b. 
Strip the insulation from the ends of the 
wires.
c. 
Using wire crimper, crimp u-type lugs on 
the ends of the wires.
 PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly 
distinguish the Live (“L”) Wire from other wires.
2.  O
pen front panel of the indoor unit.
3. 
Using a screwdriver, open the wire box cover 
on the right side of the unit. This will reveal 
the terminal block.
Terminal block
Wire cover
Screw
Cable clamp
 WARNING
4.
Unscrew the cable clamp below the terminal 
block and place it to the side.
Fig. 3.9
The Wiring Diagram is located 
on the inside of the indoor unit’s 
wire cover.
North America
Appliance Amps (A)
AWG
10 18
13 16
18 14
25 12
30 10
ALL WIRING MUST PERFORMED STRICTLY
IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED ON THE INSIDE OF THE
INDOOR UNIT S WIRE COVER.
’