CORRIGO E LON INTERFACE VARIABLE LIST MANU
8 Chapter 2 Corrigo ventilation LON-interface variable list
2.2 Table of Network Variables, Inputs (NVI)
Name SNVT type Description
nviOutdoorTemp SNVT_temp_p Outdoor temperature. Overrides signal from local sensor
nviRoomTemp
SNVT_temp_p
Room temperature. Overrides signal from local sensor
nviFullSpeedExt SNVT_switch Force to full speed (1)
nviExternalStop SNVT_switch External stop (1)
nviFireAlarm
SNVT_switch
Fire alarm (1)
nviSetPoint SNVT_temp_p Setpoint Supply air
nviCascadSetp SNVT_temp_p Setpoint cascade control. Depending on configuration
(Room temp if room control is configured,
Extract air temp if extract air control is configured)
nviMaxLimit SNVT_temp_p Max limit Supply air
nviMinLimit
SNVT_temp_p
Min limit Supply air
nviOccCmd SNVT_occupancy 0 = The unit is forced to run at 1/1-speed (3)
1 = Shut down. Support control and free cooling not active.
Frost protection active if configured
2 = Runs according to the built-in timer. Support control
and free cooling active if configured
3 = Unit stopped. Support control and free cooling active if
configured. Frost protection active if configured
nviSndHrtB SNVT_time_sec Heart Beat (0 = disable)
nviTempHyst
SNVT_temp_p
Hysteresis for variables of the type _temp_p (2)
nviCO2Hyst SNVT_ppm Hysteresis for variables of the type _ppm (CO
2
) (2)
nviPercentHyst SNVT_lev_percent Hysteresis for variables of the type _lev_percent (2)
nviPresHyst SNVT_press_p Hysteresis for variables of the type _press_p (Pressure) (2)
nviAirFlowHyst SNVT_flow_p Hysteresis for variables of the type _flow_p (Air flow) (2)
nviVoltHyst
SNVT_volt_f
Hysteresis for variables of the type _volt_f (Ao) (2)
nviSFPresSetpNor SNVT_press_p Setpoint pressure supply air fan normal operation (5)
nviEFPresSetpNor SNVT_press_p Setpoint pressure extract air fan normal operation (5)
nviSFPresSetptRed SNVT_press_p Setpoint pressure supply air fan reduced operation (5)
nviEFPresSetptRed SNVT_press_p Setpoint pressure extract air fan reduced operation (5)
nviSFAirFlowSetpNor
SNVT_flow
Setpoint flow supply air fan normal operation (5)
nviEFAirFlowSetpNor SNVT_flow Setpoint flow extract air fan normal operation (5)
nviSFAirFlowSetptRed SNVT_flow Setpoint flow supply air fan reduced operation (5)
nviEFAirFlowSetptRed SNVT_flow Setpoint flow extract air fan reduced operation (5)
nviParaTransfer SNVT_temp_p Parallel displacement of the supply air setpoint at outdoor
compensated supply air temperature control (6)