CORRIGO E LON INTERFACE VARIABLE LIST MANU
LON-interface variable list Chapter 2 Corrigo ventilation 7
Name SNVT type Description
nvoAlarm
SNVT_state_64
Bit31 – Control error Extract air fan
Bit32 – External operation Supply air fan
Bit33 – External operation Extract air fan
Bit34 – Manual running mode
Bit35 – Manual operation Supply air controller
Bit36 – Manual operation Supply air fan
Bit37 – Manual operation SAF Frequency converter
Bit38 – Manual operation Extract air fan
Bit39 – Manual operation EAF Frequency converter
Bit40 – Manual output Heating
Bit41 – Manual output Exchanger
Bit42 – Manual output Cooling
Bit43 – Manual operation P1-Heating
Bit44 – Manual operation P1-Cooling
Bit45 – Manual operation P1-Exchanger
Bit46 – Manual operation Fire damper
Bit47 – Internal Battery error
Bit48 – Sensor error Supply air temp (4)
Bit49 – Sensor error Extract air temp (4)
Bit50 – Sensor error Room temp 1 (4)
Bit51 – Sensor error Room temp 2 (4)
Bit52 – Sensor error Exhaust air temp (4)
Bit53 – Sensor error Extra sensor (4)
Bit54 – Sensor error SAF pressure (4)
Bit55 – Sensor error EAF pressure (4)
Bit56 – Sensor error De-icing temp (4)
Bit57 – Sensor error Frost protection temp (4)
Bit58 – Sensor error CO
2
(4)
Bit59 – Sensor error Humidity room (4)
Bit60 – Sensor error Humidity duct (4)
nvoRunMode SNVT_state Binary
0 = Stop
1 = Starting up
2 = Starting half speed
3 = Starting full speed
4 = Alarm delay
5 = Normal operation
6 = Support control Heating
7 = Support control Cooling
8 = CO
2
control
9 = Free cooling
10 = Full speed stop
11 = Fan stop
12 = Fire run (5)
13 = Recirculation run (5)
14 = De-icing (5)