CORRIGO E LON INTERFACE VARIABLE LIST MANU

6 Chapter 2 Corrigo ventilation LON-interface variable list
Name SNVT type Description
Bit7 Output signal Do1 Expansion unit 1 (6)
Bit8 Output signal Do2 Expansion unit 1 (6)
Bit9 Output signal Do3 Expansion unit 1 (6)
Bit10 Output signal Do4 Expansion unit 1 (6)
Bit11 Output signal Do5 Expansion unit 1 (6)
Bit12 Output signal Do6 Expansion unit 1 (6)
Bit13 Output signal Do7 Expansion unit 1 (6)
nvoVVXExchEffi
SNVT_lev_percent
Heat exchanger efficiency monitoring
nvoSetpoint SNVT_temp_p Setpoint, Supply air
nvoCascadeSetp SNVT_temp_p Setpoint cascade control. Depending on configuration
(Room temp if room control is configured,
Extract air temp if extract air control is configured)
nvoMaxLimit SNVT_temp_p Max limit Supply temperature
nvoMinLimit
SNVT_temp_p
Min limit Supply temperature
nvoAlarm
SNVT_state_64
Bit0 Run error Supply air fan
Bit1 Run error Extract air fan
Bit2 Run error P1-Heating
Bit3 Run error P1-Cooling
Bit4 Run error P1-Exchanger
Bit5 Filter guard
Bit6 Flow guard
Bit7 External frost guard
Bit8 De-icing heat exchanger
Bit9 Fire alarm
Bit10 External stop
Bit11 External alarm
Bit12 Control error Supply air controller
Bit13 Not used
Bit14 High supply air temperature
Bit15 Low supply air temperature
Bit16 Supply air max limit active
Bit17 Supply air min limit active
Bit18 Too high room temperature
Bit19 Too low room temperature
Bit20 Too high extract air temperature
Bit21 Too low extract air temperature
Bit22 Overheating protection active
Bit23 Frost risk
Bit24 Frost protection active
Bit25 Low efficiency heat exchanger
Bit26 Sensor error
Bit26 Sensor error outdoor temperature (4)
Bit27 Analogue de-icing of heat exchanger active
Bit28 Rotation guard heat exchanger
Bit28 Rotation guard heat exchanger
Bit29 Fire damper is out of operation
Bit30 Control error Supply air fan