CORRIGO E LON INTERFACE VARIABLE LIST MANU
LON-interface variable list Chapter 2 Corrigo ventilation 5
Chapter 2 Corrigo ventilation
2.1 Table of Network Variables, Outputs (NVO)
Name SNVT type Description
nvoOutdoorTemp SNVT_temp_p Outdoor temperature
nvoSuppAirTemp
SNVT_temp_p
Supply air temperature
nvoExstAirTemp SNVT_temp_p Extract air temperature
nvoRoomTemp
SNVT_temp_p
Room temperature
nvoExtraSensor SNVT_temp_p Temperature, extra sensor
nvoSAFPressure SNVT_press_p Pressure, Supply air fan
nvoEAFPressure
SNVT_press_p
Pressure, Extract air fan
nvoSAFAirflow SNVT_flow Flow, Supply air fan (l/s)
nvoEAFAirflow
SNVT_flow
Flow, Extract air fan (l/s)
nvoDeicingTemp SNVT_temp_p Temp. De-icing sensor heat exchanger
nvoFrostProtTemp SNVT_temp_p Temp. Frost protection sensor
nvoCO2
SNVT_ppm
CO
2
nvoRoomHumidity SNVT_lev_precent Room humidity
nvoRunIndication SNVT_state Bit0 – Run indication, Supply air fan
Bit1 – Run indication, Extract air fan
Bit2 – Run indication, Pump, heating
Bit3 – De-icing heat exchanger active
nvoAo1 SNVT_volt_f Output signal Ao1
nvoAo2
SNVT_volt_f
Output signal Ao2
nvoAo3 SNVT_volt_f Output signal Ao3
nvoAo4
SNVT_volt_f
Output signal Ao4
nvoAo5 SNVT_volt_f Output signal Ao5
nvoAo1Exp1 SNVT_volt_f Output signal Ao1 Expansion unit 1 (6)
nvoAo2Exp1
SNVT_volt_f
Output signal Ao2 Expansion unit 1 (6)
nvoAo3Exp1 SNVT_volt_f Output signal Ao3 Expansion unit 1 (6)
nvoAo4Exp1
SNVT_volt_f
Output signal Ao4 Expansion unit 1 (6)
nvoAo5Exp1 SNVT_volt_f Output signal Ao5 Expansion unit 1 (6)
nvoDo SNVT_state Bit0 – Output signal Do1
Bit1 – Output signal Do2
Bit2 – Output signal Do3
Bit3 – Output signal Do4
Bit4 – Output signal Do5
Bit5 – Output signal Do6
Bit6 – Output signal Do7